Assembling instructions and maintenance
22004022 - 06.13
Menu description
Description
Default BIG EXOL
User setting
4. SETTINGS
4.1
T min. S8
20°C
4.3
Puffer 1 priority
1
4.4
Puffer 1 ΔT
15°C ÷ 7°C
4.5
Puffer 1 max. temp.
60°C
4.6
Puffer 2 priority
2
4.7
Puffer 2 ΔT
15°C ÷ 7°C
4.8
Puffer 2 max. temp.
60°C
4.17
Temperature priority
40°C
4.18
Charging pause
20 min.
4.19
Increase
3°C
5. PROTECTION FUNCTIONS
5.1 System protection
5.1.1
System protection
on
5.1.2
System protection ON
120/115°C
5.2 Manifold protection
5.2.1
Manifold protection
on
5.2.2
Protezione collettore on
110°C ÷ 100°C
5.2.3
Puffer 1 max. temp.
90°C
5.2.4
Puffer 2 max. temp.
90°C
5.3 Cooling
5.3.1
Cooling
on
5.3.2
Cooling activation temp.
85°C
5.4 Antifreeze
5.4.1
Antifreeze
off
5.5 Antilock
5.5.1
Antilock R1
off
5.5.2
Antilock R2
off
5.5.3
Antilock R3
off
5.5.4
Antilock R4
off
5.5.5
Antilock R5
off
5.5.6
Antilock R6
off
5.5.7
Antilock R7
off
5.6 Manifold alarm
5.6.1
Manifold alarm
off
6. SPECIAL FUNCTIONS
6.1 Program selection
6.1.17
6.2 Punp R1 speed (solar)
6.2.1
Vel. R1
M4
6.2.2
Pump type
0-10 V
6.2.3
Pump menu
6.2.3.1
Pump
profilo 7
6.2.3.2
Output signal
normale
6.2.3.3
0-10 V off
0,7 V
6.2.3.4
0-10 V on
2,0 V
6.2.3.5
0-10 V max
10,0 V
6.2.4
Purging duration
8 sec
6.2.5
Regulation time
4 min
6.2.6
Max speed
100%
10. Control unit parameters table