Doc: I470GB10_16.docx 18/10/2016
p. 7 / 19
L1-L2-L3
L3-L2-L1
P02.01
– Value for current transformer primary. Example: with
CT
800/5 set 800.
P02.02
– Value for phase current transformer secondary. Example: with
CT
800/5 set 5.
OFF
= no display of the current.
P02.03
– Use of voltage transformers (VT) on the generator voltage measuring inputs.
P02.04
– Primary value of voltage transformers, if used.
P02.05
– Secondary value of voltage transformers, if used.
P02.06
– Phase sequence control enabling.
OFF
= no control.
Direct
= L1-L2-L3.
Inverted
= L3-L2-L1. Note: The corresponding alarms must also be enabled.
P03 - PASSWORD
UoM
Default
Range
P03.01
Enable passwords
OFF OFF-ON
P03.02
User level password
1000 0-9999
P03.03
Advanced level password
2000 0-9999
P03.04
Remote access password
OFF OFF/1-9999
P03.01
– If set to OFF, password management is deactivated; access to settings and the Commands menu is free.
P03.02
– If P03.01 is set ON, specify here the sequence needed to obtain user level access. See the Password protected access chapter.
P03.03
– As for P03.02, but referred to Advanced level access.
P03.04
– If set to a numeric value, this represents the code to be sent over the serial line before remote commands can be transmitted.
P04 – MISCELLANEOUS
(CNFn, n=1…2)
UoM
Default
Range
P04.n.01
Rated voltage
V
400
50-50000
P04.n.02
Connection type
L1-L2-L3-N
L1-L2-L3-N
L1-L2-L3
L1-N-L2
L1-N
P04.n.03
Type of voltage control
L-L L-L
L-N
L-L + L-N
P04.n.04
Rated current
A
5 1-10000
P04.n.05
Rated frequency
Hz
50 50
60
P04.n.06
Rated engine speed
RPM
1500 750-3600
P04.n.07
Rated apparent power
kVA
Aut
Aut / 1-10000
Note: This menu is divided into 2 sections, referring to the two configurations CNF1...CNF2. See the section on variable configuration management.
P04.n.01
- Rated generator voltage. Always set phase-to-phase voltage for polyphase systems.
P04.n.02
- Choice of connection type: three-phase with/without neutral, two-phase or single-phase.
P04.n.03
- Voltage checks on phase-to-phase voltages, phase voltages or both.
P04.n.04
- Rated generator current. Used to set protection thresholds in percentages.
P04.n.05
- Rated generator frequency.
P04.n.06
- Rated engine speed (RPM).
P04.n.07
- Rated apparent power of generator.
P05 - BATTERY
UoM
Default
Range
P05.01
Rated battery voltage
V
Aut
Aut / 12 / 24
P05.02
MAX voltage threshold
%
130 110-140%
P05.03
MIN voltage threshold
%
75 60-130%
P05.04
MIN/MAX voltage delay
sec
10 0-120
P05.01
- Rated battery voltage. If set to AUT, nominal battery voltage is automatically recognized during power-up.
P05.02
- MAX battery voltage alarm threshold.
P05.03
- MIN battery voltage alarm threshold.
P05.04
- MIN and MAX battery alarm delay.
P06 - ACOUSTIC ALARMS
UoM
Default
Range
P06.01
Siren sound mode on alarm
Timed
OFF
Keypad
Timed
Repeated
P06.02
Sound activation time on alarm
sec
30
OFF/1-600
P06.03
Sound activation time before starting
sec
OFF
OFF / 1-600
P06.04
Acoustic signalling device
SIREN OFF
SIREN
P06.01 - OFF
= siren deactivated.
Keypad
= Siren sounds continuously until cancelled by pressing a button on the front panel.
Timed
= Siren sounds for the time specified in
P06.02.
Repeated
= Siren sounds for the time in P06.02, pauses for three times this value, and then repeats cyclically.
P06.02
- Acoustic signal activation time on alarm.
P06.03
- Acoustic signal activation time before engine starts.
P06.04
- Acoustic signalling device enabling.
P07 – ENGINE SPEED
UoM
Default
Range
P07.01
Engine speed measurement source
W/Pick-Up
OFF
Freq-Gen.
W/Pick-Up
P07.02
RPM / W - pick-up ratio
1.000 0.001-50.000
P07.03
MAX speed threshold
%
110 80-120
P07.04
MAX speed alarm delay
sec
3.0 0.5-60.0
P07.05
MIN speed threshold
%
90 80-100
P07.06
MIN speed alarm delay
sec
5 0-600