LOVATO ELECTRIC RGK400SA Instruction Manual Download Page 4

 

 

         Doc: I470GB10_16.docx                                      18/10/2016 

p. 4 / 19 

Expandability 

 

Thanks to its expansion bus, the RGK4...SA can be expanded with additional modules of the EXP... series. 

 

The RGK400SA and RGK420SA support the EXP1040 expansion module, which provides additional 2 inputs and outputs. 

 

Program at least one of the resources which the module will make available (for instance, assign the analog input AIN2 to fuel level). 

 

To install the module, proceed as shown in the figure, with the controller switched off: 

 

 

 

 

The next time the controller is switched on, it automatically recognises the expansion module and makes the new resources available. 

 
Inputs and outputs 

 

The inputs and outputs are identified by a code and a sequential number. For example, the digital inputs are named INPx, where x is the input number. Similarly, the digital 

outputs are named OUTx.

 

 

The input/output numbering is a sequential numbering from the top down.  

 
 

CODE 

DESCRIPTION 

BASE 

EXP 

INPx 

Digital inputs 

1…6 

7...8 

OUTx 

Digital outputs 

1…5 

6…7 

   

 

User alarms (UAx) 

 

The user can define up to 2 programmable alarms (UA1…UA2). 

 

The following can be established for each alarm: 

o

 

the 

source

, i.e. the condition that generates the alarm;

  

o

 

the 

text

 of the message that appears on the display when the alarm condition occurs;

 

o

 

the 

properties

 of the alarm (as for standard alarms), i.e. how it interacts with the genset controller.

  

 

If the alarm is displayed following activation of an external digital input, then the source must be an INPx. 

 

The user can define a freely programmable message to appear on the display. 

 

Properties for user alarms can be defined using the same method applied to normal alarms. In other words, users can decide whether a given alarm must stop the engine, 
sound the siren, activate the generic alarm output etc. See the 

Alarm

 chapter.

 

 

Multiple simultaneous alarms are displayed in sequence. 

 

Use the specific command in the Commands menu to reset a programmed alarm with memory. 

 

See the settings menu to define alarms. 

 

IR programming port 

 

The parameters of the RGK4...SA may be configured via the front panel optical port using the IR-USB CX01 programming dongle or the IR-Wi-Fi CX02 dongle.  

 

Simply insert the connectors of the CX... dongle in the sockets of the port on the front panel to obtain mutual recognition of the devices, indicated by the green LINK LED lighting 

on the programming dongle.

 

          

 

USB CX01 and Wi-Fi CX02 programming dongles 

Setting parameters from a PC  

 

Xpress

 configuration and control software can be used to transfer setup parameters (previously set) from the RGK4...SA to a PC hard disk and vice versa. 

 

 

Parameter transfer from a PC to the RGK4...SA may be partial, i.e. only the parameters of specified menus will be transferred. 

 

 

 

 

Summary of Contents for RGK400SA

Page 1: ...s 3 Navigating between the display pages 3 Switching on and starting up RGK400SA 3 Switching on and starting up RGK420SA 3 Expandability 4 Inputs and outputs 4 User alarms UAx 4 IR programming port 4...

Page 2: ...eter and alarm messages in 5 languages ENG ITA FRA SPA DEU 3 Ph N 480 VAC rated generator voltage measuring input 1 ph current input 6 digital inputs including o 4 standard digital inputs o 1 digital...

Page 3: ...er only switches off at the end of this after the engine has stopped During the cooling cycle the display reads out a countdown of the time to engine shutdown If you wish to stop the engine immediatel...

Page 4: ...occurs o the properties of the alarm as for standard alarms i e how it interacts with the genset controller If the alarm is displayed following activation of an external digital input then the source...

Page 5: ...f the RGK4 SA controller more or less in the position shown alongside Hold it in position for a few seconds until you hear a beep The app runs automatically and the parameters are loaded and displayed...

Page 6: ...or voltage parameters P13 GENERATOR PROTECTION Alternator protection functions P14 DIGITAL INPUTS Programmable digital input functions P15 DIGITAL OUTPUTS Programmable digital output functions P17 MIS...

Page 7: ...ment P04 n 01 Rated generator voltage Always set phase to phase voltage for polyphase systems P04 n 02 Choice of connection type three phase with without neutral two phase or single phase P04 n 03 Vol...

Page 8: ...asurements while performing calibration P08 04 Selection of unit of measure for oil pressure P08 05 P08 06 The minimum oil pressure pre alarm and alarm thresholds respectively See the corresponding al...

Page 9: ...C P11 03 Generator frequency threshold for determining motor running P11 04 W speed or pick up signal threshold or AC from permanent magnet alternator threshold for determining motor running P11 05 Gl...

Page 10: ...ed current for alarm A31 Maximum generator current P13 02 Delay for alarm in previous parameter P13 03 Percentage threshold referred to rated current for alarm A32 Generator short circuit P13 04 Delay...

Page 11: ...of the signal the engine begins its stop cycle Start without stop Starts the engine remotely and does not stop it in the event of an alarm The signal must be maintained for as long as the engine needs...

Page 12: ...time set in P05 04 A16 Battery voltage low Occurs if battery voltage remains below the threshold set in P05 03 for longer than the time set in P05 04 A17 Battery discharged Occurs if engine start atte...

Page 13: ...Manual circuit breaker open A46 Cannot change configuration A47 Water in fuel UA1 UA1 UA2 UA2 A38 System error 5V Occurs if an internal error occurs in the RGK4 SA controller Contact Technical Support...

Page 14: ...e sensor offset Advanced Calibrates resistive sensors by adding subtracting a value in Ohms to the resistance measured by them to compensate for cable length or resistance offsets Calibration is made...

Page 15: ...K ALIMENTATO 18 12 11 13 14 L3 L1 L2 L3 24 L1 25 L2 23 S1 21 20 S2 RGK420SA 3 4 5 17 6 N N 22 19 10 9 8 F F4A ELETTROV CARBURANTE FUEL SOLENOID VALVE START AVVIAMENTO F F6A LIVELLO CARBURANTE AN MASSA...

Page 16: ...OIL PRESSURE T1A 15 16 3 4 5 17 6 LIBERO 1 2 FREE F INP5 INP6 INP4 INP3 INP2 INP1 ARRESTO DI EMERGENZA ALTERNATORI TIPO BOSCH MARELLI LUCAS PICK UP PICK UP BATTERY ALTERNATOR TYPE BOSCH MARELLI LUCAS...

Page 17: ...4 23 22 21 19 16 18 15 BATTERY 20 17 8 10 12 14 7 9 11 13 2 4 6 1 3 5 L1 L2 L3 N S1 S2 COM1 OUT2 OUT4 COM2 D OUT1 OUT3 OUT5 INP1 AN INP3 INP5 S GND INP2 INP4 100 500VLL 50 60Hz CAT III I 0 025 5A SSR...

Page 18: ...impedance 100 K Pre excited battery charging alternator 500 rpm input terminal 7 Operating range 0 33 V Max input current 1 mA Max voltage at D terminal 12 or 24 VDC battery voltage Excitation curren...

Page 19: ...max 0 2 2 5 mmq 24 12 AWG UL use data Cable cross section min max 0 75 2 5 mm 18 12 AWG Tightening torque 0 56 Nm 5 Lbin Enclosure Version Flat panel mounted Material Polycarbonate Front protection ra...

Reviews: