P17 - MISCELLANEOUS 

UoM 

Default 

Range

 

P17.01 

Maintenance interval  

OFF OFF/1-99999 

P17.02 

Rental hours pre-set 

OFF OFF/1-99999 

P17.03 

Maximum kVA alarm threshold   

OFF OFF/5-250 

P17.04 

Maximum kVA alarm delay 

sec 

0 0-9999 

P17.05 

Generator switch feedback delay 

sec 

5 1-60 

P17.01

 – This defines the programmed maintenance interval, expressed in hours. If set to OFF, the maintenance interval is deactivated.

 

P17.02

 – Number of rental hours to be pre-set in counter by command C05 Rental hours pre-set. 

P17.03…P17.04

 – Threshold and delay for alarm A34 Generator kVA threshold exceeded. 

P17.05

 – Delay for A36 alarm.  

 

P18 – USER ALARMS 
(UAn, n=1…2) 

UoM 

Default 

Range

 

P18.n.01 

Alarm source 

 

OFF OFF 

INPx 

OUTx 

P18.n.02 

Channel no. (x) 

 

OFF / 1…99 

P18.n.03 

Text  

 

UAn (text 

- 16 characters) 

Note: This menu is divided into 2 sections for defining user alarms UA1 and UA2. 
P18.n.01

 –

 

Defines the digital input or internal variable the activation of which generates the user alarm. 

P18.n.02

 – Number of channel referred to the previous parameter.  

P18.n.03

 – Free text that will appear in the alarm window. 

Example: User alarm UA2 must be generated by the closing of input INP5 and must display the ‘Doors open’ message. 
In the case, set menu section 2 (for alarm UA2) as follows: 
P18.2.01 = INPx 
P18.2.02 = 5   
P18.2.03 = ‘Doors open’ 

 
 

Programmable input functions 
 

Function 

Description 

Disabled Input 

disabled. 

Configurable Freely 

configurable by the user.  

Oil pressure  

Digital sensor for low engine oil pressure. 

Engine temperature 

Digital sensor for maximum engine coolant temperature  

Fuel level 

Digital sensor for low fuel level 

Emergency stop 

When open, generates 

A23 Emergencyy stop 

alarm.  Not needed if +COM1 is used with incorporated input. 

Remote stop 

Stops engine from remote point. 

Off load remote start 

Starts the engine remotely without transferring load to the generator. The signal must be maintained for as long as 
the engine needs to run. On deactivation of the signal, the engine begins its stop cycle. 

On load remote start 

Starts the engine remotely and connects load to the generator. The signal must be maintained for as long as the 
engine needs to run. On deactivation of the signal, the engine begins its stop cycle. 

Start without stop 

Starts the engine remotely and does not stop it in the event of an alarm. The signal must be maintained for as long 
as the engine needs to run. On deactivation of the signal, the engine begins its stop cycle. 

Generator protection 

Generator protection tripped signal from external device. 

Remote control lock       

Locks control and write operations via serial port. Data reading remains possible. 

Setup lock 

Prevents access to the programming (setup) menu. 

External GEN control 

Generator voltage control signal from external device. If active, indicates voltage within thresholds. 

Enabling of load transfer to generator 

OK to transfer load to generator. 

GEN switch feedback  

Alarm 

A36

 

Generator switch fault 

is generated in the event of discrepancy between the control output and the 

actual state. 

Keypad lock  

Locks functioning of front panel, excluding page navigation buttons. 

Genset and keypad lock 

Locks functioning of the generating set and keypad. 

Radiator coolant level 

Alarm 

A40 Radiator coolant low

 is generated when input is activated.

.

 

Siren OFF 

Disables the siren.       

Breaker state alarm 

With the input OFF, starting is prevented and alarm 

A41

 

Breaker closed

 is triggered. This function is used in 

manual control mode when the generator's remote breaker is not used and a manually operated breaker is used 
instead. This function is needed to be sure that no load is connected before the generator starts. In AUT mode, 
when the input is ON, starting is prevented and alarm 

A42

 

Breaker open

 is activated. This function is needed to 

avoid starting the generator and wasting fuel without a load. 

Alarm inhibit 

When active, disables alarms for which the 

Inhibit

 property is active. 

Reset alarms 

Resets retaining alarms the cause of which has ceased. 

Commands menu C(xx) 

Executes the command defined by the index parameter (xx). 

Simulate STOP button 

Closing the input is equivalent to pressing the button.  

Simulate START button 

Closing the input is equivalent to pressing the button. 

Configuration selection  

Selects one of the two possible configurations. See menu 

P04

 

Multiple configurations

Water in fuel 

Generates alarm 

A47 Water in fuel.

 

 
 

Programmable output functions 
 

Function 

Description 

Disabled Output 

disabled. 

 

Configurable Freely 

configurable by the user.  

Close generator switch  

Close generator remote switch command. 

Summary of Contents for RGK400SA

Page 1: ...s 3 Navigating between the display pages 3 Switching on and starting up RGK400SA 3 Switching on and starting up RGK420SA 3 Expandability 4 Inputs and outputs 4 User alarms UAx 4 IR programming port 4...

Page 2: ...eter and alarm messages in 5 languages ENG ITA FRA SPA DEU 3 Ph N 480 VAC rated generator voltage measuring input 1 ph current input 6 digital inputs including o 4 standard digital inputs o 1 digital...

Page 3: ...er only switches off at the end of this after the engine has stopped During the cooling cycle the display reads out a countdown of the time to engine shutdown If you wish to stop the engine immediatel...

Page 4: ...occurs o the properties of the alarm as for standard alarms i e how it interacts with the genset controller If the alarm is displayed following activation of an external digital input then the source...

Page 5: ...f the RGK4 SA controller more or less in the position shown alongside Hold it in position for a few seconds until you hear a beep The app runs automatically and the parameters are loaded and displayed...

Page 6: ...or voltage parameters P13 GENERATOR PROTECTION Alternator protection functions P14 DIGITAL INPUTS Programmable digital input functions P15 DIGITAL OUTPUTS Programmable digital output functions P17 MIS...

Page 7: ...ment P04 n 01 Rated generator voltage Always set phase to phase voltage for polyphase systems P04 n 02 Choice of connection type three phase with without neutral two phase or single phase P04 n 03 Vol...

Page 8: ...asurements while performing calibration P08 04 Selection of unit of measure for oil pressure P08 05 P08 06 The minimum oil pressure pre alarm and alarm thresholds respectively See the corresponding al...

Page 9: ...C P11 03 Generator frequency threshold for determining motor running P11 04 W speed or pick up signal threshold or AC from permanent magnet alternator threshold for determining motor running P11 05 Gl...

Page 10: ...ed current for alarm A31 Maximum generator current P13 02 Delay for alarm in previous parameter P13 03 Percentage threshold referred to rated current for alarm A32 Generator short circuit P13 04 Delay...

Page 11: ...of the signal the engine begins its stop cycle Start without stop Starts the engine remotely and does not stop it in the event of an alarm The signal must be maintained for as long as the engine needs...

Page 12: ...time set in P05 04 A16 Battery voltage low Occurs if battery voltage remains below the threshold set in P05 03 for longer than the time set in P05 04 A17 Battery discharged Occurs if engine start atte...

Page 13: ...Manual circuit breaker open A46 Cannot change configuration A47 Water in fuel UA1 UA1 UA2 UA2 A38 System error 5V Occurs if an internal error occurs in the RGK4 SA controller Contact Technical Support...

Page 14: ...e sensor offset Advanced Calibrates resistive sensors by adding subtracting a value in Ohms to the resistance measured by them to compensate for cable length or resistance offsets Calibration is made...

Page 15: ...K ALIMENTATO 18 12 11 13 14 L3 L1 L2 L3 24 L1 25 L2 23 S1 21 20 S2 RGK420SA 3 4 5 17 6 N N 22 19 10 9 8 F F4A ELETTROV CARBURANTE FUEL SOLENOID VALVE START AVVIAMENTO F F6A LIVELLO CARBURANTE AN MASSA...

Page 16: ...OIL PRESSURE T1A 15 16 3 4 5 17 6 LIBERO 1 2 FREE F INP5 INP6 INP4 INP3 INP2 INP1 ARRESTO DI EMERGENZA ALTERNATORI TIPO BOSCH MARELLI LUCAS PICK UP PICK UP BATTERY ALTERNATOR TYPE BOSCH MARELLI LUCAS...

Page 17: ...4 23 22 21 19 16 18 15 BATTERY 20 17 8 10 12 14 7 9 11 13 2 4 6 1 3 5 L1 L2 L3 N S1 S2 COM1 OUT2 OUT4 COM2 D OUT1 OUT3 OUT5 INP1 AN INP3 INP5 S GND INP2 INP4 100 500VLL 50 60Hz CAT III I 0 025 5A SSR...

Page 18: ...impedance 100 K Pre excited battery charging alternator 500 rpm input terminal 7 Operating range 0 33 V Max input current 1 mA Max voltage at D terminal 12 or 24 VDC battery voltage Excitation curren...

Page 19: ...max 0 2 2 5 mmq 24 12 AWG UL use data Cable cross section min max 0 75 2 5 mm 18 12 AWG Tightening torque 0 56 Nm 5 Lbin Enclosure Version Flat panel mounted Material Polycarbonate Front protection ra...

Reviews: