PROBLEM
POSSIBLE CAUSE OR
SYMPTOM
POSSIBLE FIX
Binary Select Mode
is not set to
External
.
Go to the
General Setup
menu and set
Binary Select Mode
to
External
.
Device controlling the Binary Select
signals is not working correctly.
Typically the Binary Select is controlled by a PLC and/or
switches on a panel. Check all connections and programming
logic.
The timing of the bin select logic is not
working properly.
Check the programming logic.
Weld Monitor Malfunction.
Shutdown and restart the weld monitor. If the problem persists,
contact Livingston Service.
THE EXTERNAL BIN
SELECT IS NOT
WORKING
CORRECTLY:
The weld
summary screen indicates
that weld data is being
recorded with the wrong
Binary Select.
Interlock wiring is not correct
Check all wiring for correctness. Check that all I/O voltages are
correct.
WELD MONITOR -
ACCEPT/REJECT
SIGNALS NOT
WORKING PROPERLY
PLC programming is flawed.
Call your resident PLC programmer.
10-26