MANUAL SEWAGE EJECTOR PUMPS:
The pump cord for these pumps can be plugged directly into a 

properly grounded receptacle with voltage consistent with pump 

nameplate for continuous pump operation.

CAUTION:

 This type of operation should be used only for emer-

gency use or when a large volume of water is to be pumped. 

Pump must not be allowed to run dry. If pump is run dry, it may 

damage pump and void the warranty.

MAINTENANCE

If pump does not operate properly, consult the troubleshooting 

chart. If trouble cannot be located with these steps shown, con-

sult your pump dealer or take pump to a Little Giant authorized 

service center.

CAUTION:

 When working on pump or switch, always unplug 

pump power cord in addition to removing fuse or shutting off cir-

cuit breaker before working on pump.

CLEANING IMPELLER AND VOLUTE

  1. Remove screws that hold volute to motor housing.
  2.  Remove volute and clean impeller and volute passage. Do not 

use strong solvents on impeller.

  3. Be sure impeller turns freely after cleaning.
 4. 

WARNING:

 DO NOT REMOVE IMPELLER. REMOVAL OF 

IMPELLER REQUIRES SPECIAL TOOLS AND IS TO BE DONE 

ONLY BY AN AUTHORIZED SERVICE CENTER.

    DO NOT REMOVE MOTOR HOUSING COVER. WARRANTY 

IS VOID IF MOTOR HOUSING COVER, IMPELLER OR SEALS 

HAVE BEEN REMOVED.

    ANY REPAIR ON MOTOR MUST BE DONE BY AN AUTHORIZED 

LITTLE GIANT SERVICE CENTER.

SPECIFICATIONS

Discharge Size:

  10E Series:  1-1/2" NPT Vertical

 

10S Series:  2" or 3" NPT Vertical

Intake Size:

 

10E Series:  3/4" Screened Opening

 

10S Series:  2" Diameter Opening

Pump Housing:

 Cast Iron

Volute:

 Cast 

Iron

Screen:

 10E 

Series: 

ABS

Impeller:

 

Vortex design, with pressure relief vanes

Motor:

 

Single phase induction, 1750 RPM, with auto-

matic reset thermal overload protection.

Hardware:

 

300 Series Stainless Steel

Bearing:

 

Double shielded ball

Pump Shaft Seal:

 Mechanical, spring loaded, stationary carbon 

with Nitrile boot and rotating ceramic seat.

Power Cord:

 

16 AWG 3-conductor, copper, stranded

Cooling:

 

The motor housing contains a cooling oil to 

provide cooling for the motor and to lubricate 

bearings and seals. These pumps are capable 

of operating with the motor housing partially 

exposed for extended periods of time, provid-

ing sufficient motor cooling and bearing lubri-

cation. However, for the best cooling and lon-

gest motor life, the liquid level being pumped 

should normally be above the top of the cast 

iron motor housing.

INSTALLATION

Pump must be installed in a suitable gas-tight basin which is at 

least 18" in diameter and 24" deep.
10S Series Sewage Pumps feature a 2" or 3" female NPT dis-

charge.

10E Series Effluent Pumps feature a 1-1/2" female NPT discharge.
Pump can be installed with ABS, PVC, polyethylene or galvanized 

steel pipe. Proper adapters are required to connect plastic pipe 

to pump.
Pump must be placed on a hard level surface. Never place pump 

directly on clay, earth or gravel surfaces.
A check valve must be used in the discharge line to prevent back 

flow of liquid into the basin. The check valve should be a free flow 

valve that will easily pass solids.

CAUTION:

 For best performance of check valves, when handling 

solids install in a horizontal position or at an angle or no more than 

45°. Do not install check valve in a vertical position as solids may 

settle in valve and prevent opening on start-up.
When a check valve is used, drill a relief hole (1/8" or 3/16" diam-

eter) in the discharge pipe. This hole should be located below 

the floor line between the pump discharge and the check valve. 

Unless such a relief hole is provided, the pump could “air lock” 

and will not pump water even though it will run.

WIRING

Check local electrical and building codes before installation. The 

installation must be in accordance with their regulations as well as 

the most recent National Electrical Code (NEC).
To conform to the National Electrical Code, all pumps must be 

wired with 14 AWG or larger wire. For runs to 250', 14 AWG wire 

is sufficient. For  longer runs, consult a qualified electrician or the 

factory.
Pump should be connected or wired to its own circuit with no 

other outlets or equipment in the circuit line.Fuses and circuit 

breaker should be of ample capacity in the electrical circuit. See 

chart below.

HP

VOLTAGE

FUSE OR CIRCUIT BREAKER AMPS

1/2

115

20

1/2

230

15

REMOTE FLOAT SWITCH LEVEL CONTROL

The RFS series pumps are equipped with a remote float switch 

level control. This level control is sealed in a polypropylene float 

cylinder. For automatic operation, the pump must be plugged 

or wired into a remote float switch. Pump will run continuously if 

plugged directly into an electrical outlet.
When the level rises in the basin, the cylinder floats up with the 

level. When the cylinder position is at an angle of about 45° the 

switch activates and starts the pump motor.
As the level draws down, the cylinder floats down and when it is 

again at an angle of about 45°, the switch deactivates, and the 

pump motor stops.

NOTE:

 BE CERTAIN PUMP IS SECURE IN BASIN AND CYLINDER 

FLOATS UNOBSTRUCTED WITHOUT TOUCHING THE BASIN 

WALLS OR PLUMBING.

REMOTE FLOAT SWITCH INSTALLATION

 1. The float switch consists of three parts: switch, cord clamp, 

clamp screw. 

NOTE:

 If screw is lost, use a #10-16 x 1/2” long 

tapping screw.

 2. Attach cord clamp to pump cover as shown in Figure 1. The 

clamp must be positioned as shown to allow free operation of 

float. Be sure to locate pump and switch power cords away 

from switch float.

 3. A 3-1/2" tether length is recommended. When a tether length 

of 3-1/2" is used, a minimum basin diameter of 18" is recom-

mended. The tether length is measured as shown in Figure 1.

 4. After desired tether length is established, hand-tighten 

clamp screw.

3

Summary of Contents for 10E Series

Page 1: ...filled motor housing for lifetime lubrication and rapid heat dissipation n Stainless steel fasteners n Mechanical seals stainless steel spring nitrile parts Carbon and ceramic faces n Bearings Upper...

Page 2: ...11275 UL CSA 1 2 208 230 3 4 6 6A 900 80 67 52 33 26 11 2 15 36 10 25 x 9 6 x 8 25 10E CIM 511225 UL CSA 1 2 115 3 4 10 5 900 80 67 52 33 26 11 2 25 36 10 25 x 9 6 x 8 25 All Models are 60 Hz NOTE Use...

Page 3: ...splice between the pump and the control panel must be made within a junction box and mounted outside of the basin and comply with the National Electrical Code Do not use the power cord for lifting the...

Page 4: ...33 26 11 2 15 36 10E CIM UL CSA 1 2 208 240 3 4 6 5 900 80 67 52 33 26 11 2 15 36 10E CIA RFS UL CSA 1 2 115 3 4 10 900 80 67 52 33 26 11 2 15 36 10S CIM UL CSA 1 2 115 2 12 1000 110 85 45 20 8 7 15 4...

Page 5: ...nect plastic pipe to pump Pump must be placed on a hard level surface Never place pump directly on clay earth or gravel surfaces A check valve must be used in the discharge line to prevent back flow o...

Page 6: ...rci afin qu il entre dans un panneau de commande Toute pissure entre la pompe et le panneau de commande doit tre faite l int rieur d une bo te d accouplement et install e hors du r servoir elle doit a...

Page 7: ...n 4 AVERTISSEMENT LAISSEZ LA TURBINE EN PLACE LE RETRAIT DE LA TURBINE N CESSITE DES OUTILS SP CIAUX ET NE PEUT TRE EFFECTU QU UN CENTRE DE SERVICE AUTORIS LAISSER LE COUVERCLE DU BO TIER DU MOTEUR EN...

Page 8: ...producto Guarde las instrucciones para referencia futura El producto que ha adquirido se fabrica utilizando mano de obra y materiales de la m s alta calidad y ha sido dise ado para prestarle un servi...

Page 9: ...ta el enchufe o se acorta el cable la garanti ser nula 3 Si el cable viene dotado de hilos conductores forrados como ocurre en los modelos de 230 voltios cerci rese de que los hilos conductores se enc...

Page 10: ...go El ctrico Nacional NEC m s reciente Para ajustarse a las disposiciones del C digo El ctrico Nacional todas las bombas deben tener cables 14 AWG o mayores Para recorridos 250 pies basta el cable de...

Page 11: ...6 6 5 951964 Lead Wire Red 1 1 1 1 1 1 1 1 6 901306 Screw 6 32 x 3 16 3 3 3 3 3 3 3 3 7 951963 Lead Wire Black 1 1 1 1 1 1 1 1 8 950930 Relay 115V 1 1 1 1 1 8 950934 Relay 230V 1 1 1 9 928019 Seal Rin...

Page 12: ...abierto resistencia infinita cerrado cero Loose connection in level control wiring Connexion des fils lectriques du niveau de contr le distendue Conexiones flojas en los cables del regulador de nivel...

Page 13: ...of incidental or consequential damages so the above limitation or exclusion may not apply to you This warranty gives you specific legal rights and you may also have other rights which vary from state...

Page 14: ...uesto a acci n judicial por el costo de mano de obra externa en el lugar u otros cargos incurridos por cualquier cliente al extraer o asegurar cualquier producto LITTLE GIANT pieza o componente de ste...