User Manual
Operating Instructions
2.1EN-38016-C09
for grease: Electrom agnetic switch
4 237a03
Fig. 8-3 Connection diagram without control unit, low-level control
for grease
The electromagnetic switch is activated free of wear and
free of contact by means of the magnetic field of the so-
lenoids on stirring paddle.
Technical data
Ma xim um switching capacity ................................. 60VA
Ma xim um switching voltage .................................. 230 V
Current switched ....................................................... 3 A
6001a02
NOTE
The life of the float magnetic / magnetic
circuit breaker strongly depends on the
conditions under which it is loaded. Since
the data relative to the maximum switch-
ing capacity refer to strictly resistive loads,
which cannot be always guaranteed in
practice, it is necessary to take the cor-
responding contact protection measures
in the case of deviating loads.
Mode of Operation, continuation
… for oil: Float magnetic switch
1 202a99
Fig. 8-4 Connection diagram, low-level control for oil
Operating mode
Float magnetic switches are equipped with hermetically sealed
reed contacts. The reed contacts are activated by the magnetic
field of a ring solenoid included in the float totally free of wear
and without c ontact. The only movable component of the float
magnetic switch is the float that moves up and down with the
liquid reliably on the slide tube.
Technical data
Ma xim um switching capacity ......................................... 60VA
Ma xim um switching voltage .......................................... 230 V
Current switched ............................................................... 3 A
Contact protection measures
1201a9 5
Fig. 8-5 Contact protection measures
1 - Electromagnetic switch
2 - RC element
3 - Diode
4 - Load