Page 36 of 76
Correct wiring of Power GND and Signal GND for IC Advanced and
Proportional
When using the feedback output, it is important to use the right connection setup. Attention should be paid to
the two ground connections. Power GND in the Power connector and Signal GND in the Control connector. When
using either 0-10V, Hall or PWM feedback, the Signal GND must be used. For optimal accuracy, the Signal GND
is connected to the Power GND as close as possible to the feedback input equipment.
FEEDBACK
SIGNAL GND
50%
50%
Hall
0-10V
PWM
Power
supply
Feedback
input
Power connector
Control connector
POWER
POWER GND
WHITE
VIOLET
BROWN
BLUE
50%
50%
LA33 IC actuator
FEEDBACK
4-20mA
Power
supply
Feedback
input *
Power connector
Control connector
POWER
POWER GND
LA33 IC actuator
VIOLET
BROWN
BLUE
The following connection illustration applies only for 4-20mA:
* Only to be used on differential input card. Do not use single ended input card.
Do NOT connect or put the white wire anywhere near GND, as this will create ground loops, disturbing
the mA-signal.