58
ULM.0.01.000RE_10_08_20
- current signal amplitude, and on the right following the “Min.:” word - amplitude
criterion (“Adequate signal amplitude” in the “Configuration” tab). When amplitude
is below criterion, bit 2 of the status register is set to 1.
“Measuring device test” – measurement system performance indicator; on the right
– maximum permissible value; when this is exceeded, bit 1 of the status register is
set to 1.
If the “Measuring device test” parameter maximum permissible value is exceeded,
this means the level transmitter electronic module failure. Follow repair request
procedure in accordance with para. 11 hereof.
- “Readings stability” – indicator of general stability (short- and long-term one).
- “Mode” – steady-state mode when transmitter finds steady signal, otherwise –
transient mode – test mode after switching on.
- "Supply voltage" – current and minimum permissible voltage in volts (status bit
7). Temperature inside the transmitter casing in degrees centigrade, and permissible
temperature range (status bit 10).
“Transmitter vertical deviation” – in two planes in degrees, and permissible devia-
tion (status bit 6). When permissible deviation is exceeded, transmitter leveling is
required (with water level).
“Status”
panel. For more details, see “Configurator – User's Guide”.
The
“Communications”
panel allows estimation of communication line state. As
long as “Diagnostics” tab is active, continuous data exchange with transmitter oc-
curs. Value in “Data exchanges” field must be continuously increased (from 0 to
999, and then reset to zero), values in “Communication errors” and “Check sum er-
rors” fields must not be increased subject to use of high-quality communication line.
Single errors could occur at the real facilities with the extended communication line.
The
“Equipment panel”
displays additional optional components for monitoring
the power supply, temperature, tilting angles (tilt meter) available in the device.
The
“4-20mA Output”
panel visualizes current output settings: base height (H0 -
on the right), levels/distances corresponding to the 4 and 20 mA currents (4ma_N =,
20ma_N= on the left), and current level and distance values. In addition, measure-
ment range limits are highlighted in magenta on the top and bottom.
The
“Readings”
panel displays level, distance, input and output currents, and relay
contacts positions.
!
CAUTION