Set parameters 

Keep

S

depressed for 5 seconds to enter into parameter setting status. 

At the setting status, display shows “parameter-value parameter-code”. 

Press

S

or

to select parameter code. 

Press

or

to set the value of the code. Keep depressed could fast set. 

Keep

S

for 5 seconds to save the settings and exit the setting status. 

The setting status will exit 

without

 saving the settings if there is no key operation for 15 seconds.

 

System parameter table 

Code 

Function 

Range 

Remark 

Factory Default   

t0 

Temperature control mode 

H/C 

H: heat; C: cool 

t1 

Temperature control hysteresis 

0.1 ~ 20.0

 

 

0.1 

t2 

Time delay protection for Temperature load 

0 ~ 30 min 

 

t3 

Temperature calibration 

-9.9 ~ +9.9

 

 

0.0 

t4 

Over high temperature point (relative value) 

0.0 ~ 20.0

 

If 0.0, disable the protection 

0.2 

t5 

Over high temperature hysteresis 

0.0 ~ 20.0

 

If 0.0, disable the protection 

0.1 

t6 

High temp. alarm point (relative value) 

0.0 ~ 65.0

 

If 0.0, disable the function 

0.0 

t7 

Low temp. alarm point (relative value) 

0.0 ~ 65.0

 

If 0.0, disable the function 

0.0 

h0 

Humidity control mode 

H/P 

H: humidify; P: dehumidify 

h1 

Humidity control hysteresis 

1 ~ 20%RH 

 

h2 

Time delay protection for Humidity load 

0 ~ 30 min 

 

h3 

Humidity calibration 

-20 ~ +20%RH 

 

h4 

Over high humidity point (relative value) 

0 ~ 20%RH 

If 0, disable the protection 

h5 

Over high humidity hysteresis 

0 ~ 20%RH 

If 0, disable the protection 

h6 

High humidity alarm point (relative value) 

0 ~ 80%RH 

If 0, disable the function 

h7 

Low humidity alarm point (relative value) 

0 ~ 80%RH 

If 0, disable the function 

u0 

R4 / R5 de-energized time 

~ 999 min 

If 0, stop the timer function 

60 

u1 

R4 / R5 energized time 

~ 999 sec 

If 0, stop the timer function 

30 

u2 

Times for R4 and R5 switching 

~ 999 

If 0, switching without stop 

u3 

R1 de-energized time 

0 ~ 999 min 

If 0, stop the timer function 

120 

u4 

R1 energized time 

0 ~ 999 sec 

If 0, stop the timer function 

30 

u7 

RS485 baud rate (bps) 

~ 3 

0: 2400    1: 4800 

2: 9600    3: 19200 

u8 

Modbus address 

~ 255 

 

 

u9 

Sensor selection 

0/1 

0: ZL-SHr05J; 1: ZL-SHr05P 

 

Control 

Multifunction Output R1 

Over hot / wet protection: If R1 drives an exhaustion fan, it has the function to cool down or dry quickly.   

Ref. to 

Temperature control 

-> 

Over hot protection

, and 

Humidity control

 -> 

Over wet protection

Timer output: R1 will be energized for

u4

after de-energized for

u3

, periodically. 

 

Temperature control 

Heat mode 

t0 = H

 

If 

Room temp. 

≤ 

Set temp.

 (

TP

) –

t1

, and 

Temp. Output

 (R3) has stopped for

t2

, then 

Temp. Output

 will be energized. 

If 

Room temp. 

≥ 

Set temp.

, then 

Temp. Output

 will be de-energized. 

Summary of Contents for ZL-7850R

Page 1: ...ure humidity alarm Sensor failure alarm and outputs protection Running status saving for power supply failure Calibration for temperature and humidity Temperature and humidity output delay protection Specification Power supply 100 240Vac 50 60Hz Sensor Factory provided cable length is 2 meters Accuracy Temperature 1 25 Humidity 3 with the sensor ZL SHr05J 2 with the sensor ZL SHr05P Setting range ...

Page 2: ...m hH Humidity high alarm point High humidity alarm hL Humidity low alarm point Low humidity alarm Lo Keypad locked Keypad locked Un Keypad unlocked Keypad unlocked UnL Restore to factory default settings Restoring to default settings Operation On Off Keep key depressed for 2 seconds to switch the controller between online and offline When in offline status display OF Set temperature and humidity F...

Page 3: ...me delay protection for Humidity load 0 30 min 0 h3 Humidity calibration 20 20 RH 0 h4 Over high humidity point relative value 0 20 RH If 0 disable the protection 5 h5 Over high humidity hysteresis 0 20 RH If 0 disable the protection 2 h6 High humidity alarm point relative value 0 80 RH If 0 disable the function 0 h7 Low humidity alarm point relative value 0 80 RH If 0 disable the function 0 u0 R4...

Page 4: ...nd R5 will be energized for u1 time alternatively A period includes an R4 energized and an R5 energized There is a counter counting the times of the period Every time after the power supplied the counting value is reset to zero keeping S and depressed simultaneously will show the counting value for 3 seconds If u2 0 when the counting value reaches u2 R4 and R5 will stop energized and display and w...

Page 5: ... settings will restore to factory default set value Attention 1 Do not connect wiring when power is supplied 2 Electrical wiring must be manipulated by certified electrician 3 Read this manual carefully Connect according to electrical wiring diagram Wrong connection will damage the device 4 Do not lay the sensor bundle together with power supply bundle 5 Avoid working in erosive wet strong electri...

Page 6: ...ed 1 energized 0x01 15 bit R2 status R 0 de energized 1 energized 0x01 16 bit R3 status R 0 de energized 1 energized 0x01 17 bit R4 status R 0 de energized 1 energized 0x01 18 bit R5 status R 0 de energized 1 energized 0x01 20 bit R4 is forced energized manually R 0 not forced 1 forced energized 0x01 21 bit R5 is forced energized manually R 0 not forced 1 forced energized 0x01 22 bit Timing moment...

Page 7: ...is R W 1 0 20 0 RH 2 0 Value 10 0x03 0x06 0x10 19 int h2 Delay protection for humidity load R W 0 30 Min 0 0x03 0x06 0x10 20 int h3 Humidity calibration R W 20 0 20 0 RH 0 0 Value 10 0x03 0x06 0x10 21 int h4 Over high humidity point R W 0 0 20 0 RH 5 0 Value 10 0x03 0x06 0x10 22 int h5 Over high humidity hysteresis R W 0 0 20 0 RH 2 0 Value 10 0x03 0x06 0x10 23 int h6 High humidity alarm point R W...

Reviews: