Suzhou Lily Tech. CO., Ltd.
Page 3, Total 7 Pages
Set parameters
Keep
〖
S
〗
depressed for 5 seconds to enter into parameter setting status.
At the setting status, display shows “parameter-value parameter-code”.
Press
〖
S
〗
or
〖
〗
to select parameter code.
Press
〖
▲
〗
or
〖
▼
〗
to set the value of the code. Keep depressed could fast set.
Keep
〖
S
〗
for 5 seconds to save the settings and exit the setting status.
The setting status will exit
without
saving the settings if there is no key operation for 15 seconds.
System parameter table
Code
Function
Range
Remark
Factory Default
t0
Temperature control mode
H/C
H: heat; C: cool
H
t1
Temperature control hysteresis
0.1 ~ 20.0
℃
0.1
t2
Time delay protection for Temperature load
0 ~ 30 min
0
t3
Temperature calibration
-9.9 ~ +9.9
℃
0.0
t4
Over high temperature point (relative value)
0.0 ~ 20.0
℃
If 0.0, disable the protection
0.2
t5
Over high temperature hysteresis
0.0 ~ 20.0
℃
If 0.0, disable the protection
0.1
t6
High temp. alarm point (relative value)
0.0 ~ 65.0
℃
If 0.0, disable the function
0.0
t7
Low temp. alarm point (relative value)
0.0 ~ 65.0
℃
If 0.0, disable the function
0.0
h0
Humidity control mode
H/P
H: humidify; P: dehumidify
H
h1
Humidity control hysteresis
1 ~ 20%RH
2
h2
Time delay protection for Humidity load
0 ~ 30 min
0
h3
Humidity calibration
-20 ~ +20%RH
0
h4
Over high humidity point (relative value)
0 ~ 20%RH
If 0, disable the protection
5
h5
Over high humidity hysteresis
0 ~ 20%RH
If 0, disable the protection
2
h6
High humidity alarm point (relative value)
0 ~ 80%RH
If 0, disable the function
0
h7
Low humidity alarm point (relative value)
0 ~ 80%RH
If 0, disable the function
0
u0
R4 / R5 de-energized time
0
~ 999 min
If 0, stop the timer function
60
u1
R4 / R5 energized time
0
~ 999 sec
If 0, stop the timer function
30
u2
Times for R4 and R5 switching
0
~ 999
If 0, switching without stop
0
u3
R1 de-energized time
0 ~ 999 min
If 0, stop the timer function
120
u4
R1 energized time
0 ~ 999 sec
If 0, stop the timer function
30
u7
RS485 baud rate (bps)
0
~ 3
0: 2400 1: 4800
2: 9600 3: 19200
2
u8
Modbus address
1
~ 255
1
u9
Sensor selection
0/1
0: ZL-SHr05J; 1: ZL-SHr05P
0
Control
Multifunction Output R1
Over hot / wet protection: If R1 drives an exhaustion fan, it has the function to cool down or dry quickly.
Ref. to
Temperature control
->
Over hot protection
, and
Humidity control
->
Over wet protection
.
Timer output: R1 will be energized for
【
u4
】
after de-energized for
【
u3
】
, periodically.
Temperature control
Heat mode
【
t0 = H
】
If
Room temp.
≤
Set temp.
(
TP
) –
【
t1
】
, and
Temp. Output
(R3) has stopped for
【
t2
】
, then
Temp. Output
will be energized.
If
Room temp.
≥
Set temp.
, then
Temp. Output
will be de-energized.