Suzhou Lily Tech. CO., Ltd. 

Page  7,    Total  7  Pages 

 

Register table 

Register 

Address 

Type 

Remark 

R/W 

Value 

Unit 

Default 

Remark 

Modbus 

Command 

int 

Room temp. 

-20.0 ~ 80.0 

 

 

 

Value * 10 

0x03 

int 

Room humidity 

0.0 ~ 99.0 

%RH 

 

 

Value * 10 

0x03 

int 

R4/R5 De-energized time 

0 ~ 999 

Min 

 

 

 

 

0x03 

int 

R4/R5 Energized time 

0 ~ 999 

Sec 

 

 

 

 

0x03 

int    R1 De-energized time 

0 ~ 999 

Min 

 

 

 

 

0x03 

int 

R1 Energized time 

0 ~ 999 

Sec 

 

 

 

 

0x03 

int 

t0 Cool/heat mode 

R/W 

12/22 

 

 

22 

12: cool,   

22: heat 

0x03/0x06/0x10 

10 

int 

t1 Temp. hysteresis 

R/W 

0.1 ~ 20.0   

 

0.1 

Value * 10 

0x03/0x06/0x10 

11 

int 

t2 Delay protection for temp. load 

R/W 

0 ~ 30 

Min 

 

0x03/0x06/0x10 

12 

int 

t3 Temp. calibration 

R/W 

-9.9 ~ +9.9 

 

Value * 10 

0x03/0x06/0x10 

13 

int 

t4 Over high temp. point 

R/W 

0.0 ~ 20.0   

 

0.2 

Value * 10 

0x03/0x06/0x10 

14 

int 

t5 Over high temp. hysteresis 

R/W 

0.0 ~ 20.0   

 

0.1 

Value * 10 

0x03/0x06/0x10 

15 

int 

t6 High temp. alarm point 

R/W 

0.0 ~ 65.0   

 

Value * 10 

0x03/0x06/0x10 

16 

int 

t7 Low temp. alarm point 

R/W 

0.0 ~ 65.0   

 

Value * 10 

0x03/0x06/0x10 

17 

int 

h0 Humidify/de-humidify mode 

R/W 

17/22 

 

 

22 

17: dry,   

22: humidify 

0x03/0x06/0x10 

18 

int 

h1 Humidify hysteresis 

R/W 

1.0 ~ 20.0

 

%RH 

2.0 

Value * 10 

0x03/0x06/0x10 

19 

int 

h2 Delay protection for humidity load 

R/W 

0 ~ 30 

Min 

 

 

0x03/0x06/0x10 

20 

int 

h3 Humidity calibration 

R/W 

-20.0 ~ +20.0 

%RH 

0.0 

Value * 10 

0x03/0x06/0x10 

21 

int 

h4 Over high humidity point 

R/W 

0.0 ~ 20.0 

%RH 

5.0 

Value * 10 

0x03/0x06/0x10 

22 

int 

h5 Over high humidity hysteresis 

R/W 

0.0 ~ 20.0 

%RH 

2.0 

Value * 10 

0x03/0x06/0x10 

23 

int 

h6 High humidity alarm point 

R/W 

0.0 ~ 80.0   

%RH 

0.0 

Value * 10 

0x03/0x06/0x10 

24 

int 

h7 Low humidity alarm point 

R/W 

0.0 ~ 80.0   

%RH 

0.0 

Value * 10 

0x03/0x06/0x10 

25 

int 

u0 R4/R5 De-energized time 

R/W 

0 ~ 999 

Min 

60 

 

 

0x03/0x06/0x10 

26 

int 

u1 R4/R5 Energized time 

R/W 

0 ~ 999 

Sec 

30 

 

 

0x03/0x06/0x10 

27 

int 

u2 Allowed times for R4/R5 period 

R/W 

0 ~ 999 

 

 

 

0x03/0x06/0x10 

28 

int 

u3 R1 De-energized time 

R/W 

0 ~ 999 

Min 

120 

 

 

0x03/0x06/0x10 

29 

int 

u4 R1 Energized time 

R/W 

0 ~ 999 

Sec 

30 

 

 

0x03/0x06/0x10 

30 

int 

u7 RS485 baud rate (bps) 

R/W 

0 ~ 3 

 

 

 

 

0x03/0x06/0x10 

31 

int 

u8 Modbus address 

R/W 

1 ~ 255 

 

 

 

 

0x03/0x06/0x10 

32 

int 

u9 Sensor selection 

R/W 

0/1 

 

 

 

 

0x03/0x06/0x10 

33 

int 

Temp. set point 

R/W 

0.0 ~ 65.0   

 

37.8 

Value * 10 

0x03/0x06/0x10 

34 

int 

Humidity set point 

R/W 

0.0 ~ 99.0

 

%RH 

60.0 

Value * 10 

0x03/0x06/0x10 

35 

int 

Counter for R4/R5 period 

R/W 

0 ~ 999 

 

 

 

 

0x03/0x06/0x10 

36 

int 

Restore to factory default settings 

R/W 

0/1 

 

 

1: restoring 

0x03/0x06/0x10 

 

Summary of Contents for ZL-7850R

Page 1: ...ure humidity alarm Sensor failure alarm and outputs protection Running status saving for power supply failure Calibration for temperature and humidity Temperature and humidity output delay protection Specification Power supply 100 240Vac 50 60Hz Sensor Factory provided cable length is 2 meters Accuracy Temperature 1 25 Humidity 3 with the sensor ZL SHr05J 2 with the sensor ZL SHr05P Setting range ...

Page 2: ...m hH Humidity high alarm point High humidity alarm hL Humidity low alarm point Low humidity alarm Lo Keypad locked Keypad locked Un Keypad unlocked Keypad unlocked UnL Restore to factory default settings Restoring to default settings Operation On Off Keep key depressed for 2 seconds to switch the controller between online and offline When in offline status display OF Set temperature and humidity F...

Page 3: ...me delay protection for Humidity load 0 30 min 0 h3 Humidity calibration 20 20 RH 0 h4 Over high humidity point relative value 0 20 RH If 0 disable the protection 5 h5 Over high humidity hysteresis 0 20 RH If 0 disable the protection 2 h6 High humidity alarm point relative value 0 80 RH If 0 disable the function 0 h7 Low humidity alarm point relative value 0 80 RH If 0 disable the function 0 u0 R4...

Page 4: ...nd R5 will be energized for u1 time alternatively A period includes an R4 energized and an R5 energized There is a counter counting the times of the period Every time after the power supplied the counting value is reset to zero keeping S and depressed simultaneously will show the counting value for 3 seconds If u2 0 when the counting value reaches u2 R4 and R5 will stop energized and display and w...

Page 5: ... settings will restore to factory default set value Attention 1 Do not connect wiring when power is supplied 2 Electrical wiring must be manipulated by certified electrician 3 Read this manual carefully Connect according to electrical wiring diagram Wrong connection will damage the device 4 Do not lay the sensor bundle together with power supply bundle 5 Avoid working in erosive wet strong electri...

Page 6: ...ed 1 energized 0x01 15 bit R2 status R 0 de energized 1 energized 0x01 16 bit R3 status R 0 de energized 1 energized 0x01 17 bit R4 status R 0 de energized 1 energized 0x01 18 bit R5 status R 0 de energized 1 energized 0x01 20 bit R4 is forced energized manually R 0 not forced 1 forced energized 0x01 21 bit R5 is forced energized manually R 0 not forced 1 forced energized 0x01 22 bit Timing moment...

Page 7: ...is R W 1 0 20 0 RH 2 0 Value 10 0x03 0x06 0x10 19 int h2 Delay protection for humidity load R W 0 30 Min 0 0x03 0x06 0x10 20 int h3 Humidity calibration R W 20 0 20 0 RH 0 0 Value 10 0x03 0x06 0x10 21 int h4 Over high humidity point R W 0 0 20 0 RH 5 0 Value 10 0x03 0x06 0x10 22 int h5 Over high humidity hysteresis R W 0 0 20 0 RH 2 0 Value 10 0x03 0x06 0x10 23 int h6 High humidity alarm point R W...

Reviews: