Suzhou Lily Tech. CO., Ltd.
Page 7, Total 7 Pages
Register table
Register
Address
Type
Remark
R/W
Value
Unit
Default
Remark
Modbus
Command
1
int
Room temp.
R
-20.0 ~ 80.0
℃
Value * 10
0x03
2
int
Room humidity
R
0.0 ~ 99.0
%RH
Value * 10
0x03
3
int
R4/R5 De-energized time
R
0 ~ 999
Min
0x03
4
int
R4/R5 Energized time
R
0 ~ 999
Sec
0x03
5
int R1 De-energized time
R
0 ~ 999
Min
0x03
6
int
R1 Energized time
R
0 ~ 999
Sec
0x03
9
int
t0 Cool/heat mode
R/W
12/22
22
12: cool,
22: heat
0x03/0x06/0x10
10
int
t1 Temp. hysteresis
R/W
0.1 ~ 20.0
℃
0.1
Value * 10
0x03/0x06/0x10
11
int
t2 Delay protection for temp. load
R/W
0 ~ 30
Min
0
0x03/0x06/0x10
12
int
t3 Temp. calibration
R/W
-9.9 ~ +9.9
℃
0
Value * 10
0x03/0x06/0x10
13
int
t4 Over high temp. point
R/W
0.0 ~ 20.0
℃
0.2
Value * 10
0x03/0x06/0x10
14
int
t5 Over high temp. hysteresis
R/W
0.0 ~ 20.0
℃
0.1
Value * 10
0x03/0x06/0x10
15
int
t6 High temp. alarm point
R/W
0.0 ~ 65.0
℃
0
Value * 10
0x03/0x06/0x10
16
int
t7 Low temp. alarm point
R/W
0.0 ~ 65.0
℃
0
Value * 10
0x03/0x06/0x10
17
int
h0 Humidify/de-humidify mode
R/W
17/22
22
17: dry,
22: humidify
0x03/0x06/0x10
18
int
h1 Humidify hysteresis
R/W
1.0 ~ 20.0
%RH
2.0
Value * 10
0x03/0x06/0x10
19
int
h2 Delay protection for humidity load
R/W
0 ~ 30
Min
0
0x03/0x06/0x10
20
int
h3 Humidity calibration
R/W
-20.0 ~ +20.0
%RH
0.0
Value * 10
0x03/0x06/0x10
21
int
h4 Over high humidity point
R/W
0.0 ~ 20.0
%RH
5.0
Value * 10
0x03/0x06/0x10
22
int
h5 Over high humidity hysteresis
R/W
0.0 ~ 20.0
%RH
2.0
Value * 10
0x03/0x06/0x10
23
int
h6 High humidity alarm point
R/W
0.0 ~ 80.0
%RH
0.0
Value * 10
0x03/0x06/0x10
24
int
h7 Low humidity alarm point
R/W
0.0 ~ 80.0
%RH
0.0
Value * 10
0x03/0x06/0x10
25
int
u0 R4/R5 De-energized time
R/W
0 ~ 999
Min
60
0x03/0x06/0x10
26
int
u1 R4/R5 Energized time
R/W
0 ~ 999
Sec
30
0x03/0x06/0x10
27
int
u2 Allowed times for R4/R5 period
R/W
0 ~ 999
0
0x03/0x06/0x10
28
int
u3 R1 De-energized time
R/W
0 ~ 999
Min
120
0x03/0x06/0x10
29
int
u4 R1 Energized time
R/W
0 ~ 999
Sec
30
0x03/0x06/0x10
30
int
u7 RS485 baud rate (bps)
R/W
0 ~ 3
2
0x03/0x06/0x10
31
int
u8 Modbus address
R/W
1 ~ 255
1
0x03/0x06/0x10
32
int
u9 Sensor selection
R/W
0/1
0
0x03/0x06/0x10
33
int
Temp. set point
R/W
0.0 ~ 65.0
℃
37.8
Value * 10
0x03/0x06/0x10
34
int
Humidity set point
R/W
0.0 ~ 99.0
%RH
60.0
Value * 10
0x03/0x06/0x10
35
int
Counter for R4/R5 period
R/W
0 ~ 999
0
0x03/0x06/0x10
36
int
Restore to factory default settings
R/W
0/1
0
1: restoring
0x03/0x06/0x10