Communication 

Port setting 

Mode: Serial Asynchronous half duplex 

Baud rate (bps): 2400, 4800, 9600(default), or 19200   

Data bit: 8 (LSB 1st)   

Parity check: none   

Start bit: 1   

Stop bit: 1 

 

Modbus function 

Coil table 

Coil 

Address   

Type 

Description 

R/W 

Remark 

Modbus 

Command 

bit 

Sensor failure 

0: no problem, 1: fail 

0x01 

bit 

High temperature alarm 

0: no alarm, 1: alarm 

0x01 

bit 

Low temperature alarm 

0: no alarm, 1: alarm 

0x01 

bit 

High humidity alarm 

0: no alarm, 1: alarm 

0x01 

bit 

Low humidity alarm 

0: no alarm, 1: alarm 

0x01 

12 

bit 

R4/R5 period counting reached to U2 

0: not reached, 1: reached 

0x01 

14 

bit 

R1 status 

0: de-energized, 1: energized 

0x01 

15 

bit 

R2 status 

0: de-energized, 1: energized 

0x01 

16 

bit 

R3 status 

0: de-energized, 1: energized 

0x01 

17 

bit 

R4 status 

0: de-energized, 1: energized 

0x01 

18 

bit 

R5 status 

0: de-energized, 1: energized 

0x01 

20 

bit 

R4 is forced energized manually 

0: not forced, 1: forced energized 

0x01 

21 

bit 

R5 is forced energized manually 

0: not forced, 1: forced energized 

0x01 

22 

bit 

Timing moment for R4 or R5 

0: timing for R5, 1: timing for R4 

0x01 

25 

bit 

Controller on/offline 

R/W  0: offline, 1: online 

0x01/0x05 

26 

bit 

Keypad lock 

R/W  0: unlocked, 1: locked 

0x01/0x05 

29 

bit 

R4/R5 period counting reset 

Write 1 will clear the counter value 

0x05 

30 

bit 

Force control R4 

Write 1, R4 will be energized for U1 time 
Write 0, de-energize R4 

0x05 

31 

bit 

Force control R5 

Write 1, R5 will be energized for U1 time 
Write 0, de-energize R5 

0x05 

 

Register table (see next page) 

 

 

 

 

 

 

 

 

Summary of Contents for ZL-7850R

Page 1: ...ure humidity alarm Sensor failure alarm and outputs protection Running status saving for power supply failure Calibration for temperature and humidity Temperature and humidity output delay protection Specification Power supply 100 240Vac 50 60Hz Sensor Factory provided cable length is 2 meters Accuracy Temperature 1 25 Humidity 3 with the sensor ZL SHr05J 2 with the sensor ZL SHr05P Setting range ...

Page 2: ...m hH Humidity high alarm point High humidity alarm hL Humidity low alarm point Low humidity alarm Lo Keypad locked Keypad locked Un Keypad unlocked Keypad unlocked UnL Restore to factory default settings Restoring to default settings Operation On Off Keep key depressed for 2 seconds to switch the controller between online and offline When in offline status display OF Set temperature and humidity F...

Page 3: ...me delay protection for Humidity load 0 30 min 0 h3 Humidity calibration 20 20 RH 0 h4 Over high humidity point relative value 0 20 RH If 0 disable the protection 5 h5 Over high humidity hysteresis 0 20 RH If 0 disable the protection 2 h6 High humidity alarm point relative value 0 80 RH If 0 disable the function 0 h7 Low humidity alarm point relative value 0 80 RH If 0 disable the function 0 u0 R4...

Page 4: ...nd R5 will be energized for u1 time alternatively A period includes an R4 energized and an R5 energized There is a counter counting the times of the period Every time after the power supplied the counting value is reset to zero keeping S and depressed simultaneously will show the counting value for 3 seconds If u2 0 when the counting value reaches u2 R4 and R5 will stop energized and display and w...

Page 5: ... settings will restore to factory default set value Attention 1 Do not connect wiring when power is supplied 2 Electrical wiring must be manipulated by certified electrician 3 Read this manual carefully Connect according to electrical wiring diagram Wrong connection will damage the device 4 Do not lay the sensor bundle together with power supply bundle 5 Avoid working in erosive wet strong electri...

Page 6: ...ed 1 energized 0x01 15 bit R2 status R 0 de energized 1 energized 0x01 16 bit R3 status R 0 de energized 1 energized 0x01 17 bit R4 status R 0 de energized 1 energized 0x01 18 bit R5 status R 0 de energized 1 energized 0x01 20 bit R4 is forced energized manually R 0 not forced 1 forced energized 0x01 21 bit R5 is forced energized manually R 0 not forced 1 forced energized 0x01 22 bit Timing moment...

Page 7: ...is R W 1 0 20 0 RH 2 0 Value 10 0x03 0x06 0x10 19 int h2 Delay protection for humidity load R W 0 30 Min 0 0x03 0x06 0x10 20 int h3 Humidity calibration R W 20 0 20 0 RH 0 0 Value 10 0x03 0x06 0x10 21 int h4 Over high humidity point R W 0 0 20 0 RH 5 0 Value 10 0x03 0x06 0x10 22 int h5 Over high humidity hysteresis R W 0 0 20 0 RH 2 0 Value 10 0x03 0x06 0x10 23 int h6 High humidity alarm point R W...