Suzhou Lily Tech. CO., Ltd.
Page 4, Total 7 Pages
Cool mode
【
t0 = C
】
If
Room temp.
≥
Set temp.
+
【
t1
】
, and
Temp. Output
has stopped for
【
t2
】
, then
Temp. Output
will be energized.
If
Room temp.
≤
Set temp.
, then
Temp. Output
will be de-energized.
Over hot protection
If
Room temp.
≥
Set temp.
+
【
t4
】
, then output R1 will be energized.
If
Room temp.
≤
Set temp.
+
【
t4
】
-
【
t5
】
, then output R1 will be de-energized.
This protection function is only effective in heat mode.
If
【
t4
】
=
【
t5
】
= 0.0, disable the protection function.
Humidity control
Humidify mode
【
h0 = H
】
If
Room humidity
≤
Set humidity
(
HP
) -
【
h1
】
, and
Humi. Output
(R2) has stopped for
【
h2
】
, then
Humi. Output
will be
energized.
If
Room humidity
≥
Set humidity
, then
Humi. Output
will be de-energized.
Dehumidify mode
【
h0 = P
】
If
Room humidity
≥
Set humidity
+
【
h1
】
, and
Humi. Output
has stopped for
【
h2
】
, then
Humi. Output
will be energized.
If
Room humidity
≤
Set humidity
, then
Humi. Output
will be de-energized.
Over wet protection
If
Room humidity
≥
Set humidity
+
【
h4
】
, then output R1 will be energized.
If
Room humidity
≤
Set humidity
+
【
h4
】
-
【
h5
】
, then output R1 will be de-energized.
This protection function is only effective in humidify mode.
If
【
h4
】
=
【
h5
】
= 0.0, disable the protection function.
Timer output R4 and R5
R4 and R5 are controlled by parameter
【
u0
】
,
【
u1
】
and
【
u2
】
.
R4 and R5 will be energized for
【
u1
】
time alternatively. A period includes an R4 energized and an R5 energized.
There is a counter counting the times of the period. Every time after the power supplied, the counting value is reset to zero.
keeping
【
S
】
and
【
▼
】
depressed simultaneously will show the counting value for 3 seconds.
If
【
u2
】
> 0, when the counting value reaches
【
u2
】
, R4 and R5 will stop energized, and display
and
will blink.
If
【
u2
】
is set to zero,R4 and R5 will never stop energized.
Forced energized manually:
Keeping
【
▲
】
depressed for 2 seconds makes R5 being energized, until the key is released.
Keeping
【
▼
】
depressed for 2 seconds makes R4 being energized, until the key is released.
R4 and R5 could be used for incubator egg tray control.
Alarm
High temp. alarm: if
Room temp.
≥
Set temp.
(
TP
) +
【
t6
】
, display “tHi”. If
【
t6
】
= 0.0, the function disable.
Low temp. alarm: if
Room temp.
≤
Set temp.
-
【
t7
】
, display “tLo”. If
【
t7
】
= 0.0, the function disable.
High humidity alarm: if
Room humidity
≥
Set humidity
(
HP
) +
【
h6
】
, display “hH”. If
【
h6
】
= 0.0, the function disable.
Low humidity alarm: if
Room humidity
≤
Set humidity
-
【
h7
】
, display “hL”. If
【
h7
】
= 0.0, the function disable.
Sensor
The
Room temp.
can be calibrated. If
Room temp.
is 0.2
℃
lower than real temp., set
【
t3
】
= 0.2.
The
Room humidity
can be calibrated. If
Room humidity
is 2%RH higher than real, set
【
h3
】
= -2.
When sensor fails, the
Temp. and Humi. Output
(R3, R2) will not be energized, and “E01” will display.
Note: do not plug in/off the sensor when power supplied.