LD25x
The following operational parameters provide setting of the switching
thresholds:
Menu
Setting Range
Default
PrES_1
Preselection 1
-199999 ...
999999
10000
PrES_2
Preselection 2
-199999 ...
999999
5000
The working direction of the Hysteresis depends on the setting of the switching
characteristics.
With settings
„GE“
or
„LE“
respectively, the following switch points will result:
Preselection
Hysteresis
GE=Greater/Equal
Display Value
Hysteresis effect with "Greater / Equal"
Preselection
LE=Lower/Equal
Hysteresis
Display Value
Hysteresis effect with "Lower / Equal"
It is possible to check up on the actual switching state of the outputs at any
time.
For this, just tap on the
ENTER
key shortly.
The display will then show for the next two seconds one of the following
information:
Display
Meaning
1_2oFF
Both outputs are actually off.
1_2on
Both outputs are actually on.
1 on
Output 1 is on.
Output 2 is off.
2on
Output 1 is off.
Output 2 is on.
MAN LD25x E 1.0.odt
Set-up procedure
22 of 44