10.3
Pull Force
Recommended strength of screw attachment when installing wall profiles
Screws attached to the building must withstand a Pull Force not less than 0.5 kN each.
(See next page forexamples of screw attachments)
Minimum three screws must be used for each Wall Profile.
Note
: If the strength of screw, attachment is validated by test, minimum withdrawal
strength is 1.5 kN.