background image

7

  

(13)

inDOMO HP

 - Platform lift

FINAL TESTS

IM.TEC.028.EN_rev.10.2

   -  November 2015

All rights reserved

2.13   “STOP”  (if present ) AND ALARM BUTTONS

Check if the STOP button actually stops the lift and the alarm button activates the acoustic signal:

i.  

stop the can between two stops, using the STOP button (if available, in case of doorless car);

ii.   try to move the car upwards and downwards: 

the lift will not respond

;

iii.   repeat the commands from the landing operation panels: 

the busy signal is on and the car does not respond

iv.   push the alarm button: 

the alarm signal will be activated

;

v.   refresh.

2.14   EMERGENCY POWER SUPPLY

Check the efficiency of the emergency power circuit:

i.  

bring the car to the upper floor;

ii.   close the power supply by means of opening the main switch of the lift (not that of the Driving Force), in order to 

simulate a black-out;

iii.  

the car emergency lighting will be activated

;

iv.   push the alarm button: 

the alarm acoustic signal will be heard

;

v.   press and hold any operation button, 

the car will descend to the lowest floor, so the door can be open

;

vi.   refresh.

2.15  SHAFT CLOSURE

The shaft must be closed completely.

2.16 COMMANDS

Check the correct execution of the following commands:

i.  

a person in car will try to send the lift to each of the stops (upwards and downwards), checking if the car stops 

automatically;

ii.   upon an early release of the button (without car doors), the lift will stop immediately; within the levelling zone the 

travel will continue until an unforced stop at the landing level;

iii.   test the call from each of the stops, to check the regular automatic stops and the function of busy/present signals.

2.17   CEILING CONTACT

Check if the ceiling opening activates the safety chain:

i.  

with the car at the upper stop, unscrew the safety fixings of the removable lid;

ii.   push the call button at the lowest floor and (with the car moving) try to lift the ceiling at the COP side: 

the lift will 

stop

;

iii.   refresh.

2.18   COP CONTACT

Check if the COP opening activates the safety chain:

i.  

unscrew the fixings of the removable part of the COP;

ii.   press any of the car buttons: 

the car will not move

.

iii.   refresh.

Summary of Contents for InDomo HP

Page 1: ...a Caduti del Lavoro 16 43058 Bogolese Sorbolo PR Italy Phone 39 0521 695311 Fax 39 0521 695313 www verticogroup it info liftingitalia it 1 13 IM TEC 028 EN_rev 10 2 November 2015 inDOMOHP Platform lif...

Page 2: ...5 2 4 ORIGINAL MATERIALS FROM LIFTINGITALIA 5 2 5 STRUCTURAL TEST 5 2 6 MAXIMUM STATIC PRESSURE 5 2 7 HYDRAULIC CIRCUIT 5 2 8 BLOCK VALVE 5 2 9 OVERLOAD MANOSTAT 6 2 10 ASCENT AND DESCENT SPEED 6 2 11...

Page 3: ...due to sharp angles or protruding parts Risk of damage to mechanical parts e g during incorrect installation Fire hazard Hanging load Risk of skin injury Risk of falling No entry Materials to be prot...

Page 4: ...y each of them contains the requirements to be matched and the way to check them The operations described in this paragraph can be carried out by adequately qualified personnel The below listed operat...

Page 5: ...mities of the lift MAXIMUM LOAD 2 6 MAXIMUM STATIC PRESSURE Check the maximum static pressure with the maximum load i bring the car to the upper stop and open the valve of the pressure gauge ii Pay at...

Page 6: ...ecision either fully loaded or empty car i use the landing operation panel for commands ii with a loaded car command an upwards travel letting the lift stop by itself iii open the landing door and wit...

Page 7: ...ess and hold any operation button the car will descend to the lowest floor so the door can be open vi refresh 2 15 SHAFT CLOSURE The shaft must be closed completely 2 16 COMMANDS Check the correct exe...

Page 8: ...he shaft wall in front of the entrance ii CAR WITHOUT DOORS the distance between the shaft and the entrances must be max 20 mm valid for the full travel height ii CAR WITH DOORS the horizontal distanc...

Page 9: ...ximum 1 4 maximum static pressure described in the paragraph 2 4 of this manual v refresh 2 26 PULLEY SAFETY COVERS Check the presence and the correct assembly of the safety covers applied on the pull...

Page 10: ...ons and humidity and can keep the constant temperature comprised between 5 and 40 C ii the area in front of the cabinet door is clean and its width and height are suffucient for a safe access iii a re...

Page 11: ...ner ____________________________________________ Address ___________________________________________ ___________________________________________ Ph ______________________ Fax ____________________ Inst...

Page 12: ...____________________________________ __________________________________________________________________ __________________________________________________________________ Date _______________ Installe...

Page 13: ..._______________________________________________ __________________________________________________________________ __________________________________________________________________ Date _____________...

Reviews: