background image

Servicing  your  HRV  on  a  regular  schedule  will  result 

in  optimum  operating  efficiencies  and  prolonged  life 

of  the equipment.
Due  to  numerous  applications  in  which  this 

equipment  can  be  installed,  it  is  difficult  to  predict 

servicing  intervals.  In certain situations where there is 

heavy  smoke,  servicing  the  equipment  every  one  - 

two  months  may  be  needed;  whereas  ventilating  a 

meeting  room  for  carbon  dioxide  may  only  need 

service every six months to a year.

Motor

Access to the motor is through the front service doors. 

Note heat exchanger core can be removed to provide 

more room. See 

CORE 

in this section.

The  motor  is  a  permanent  split  capacitor  type  (PSC) 

which  uses  a  sleeve  mechanism  to  steady  the  shaft. 

Core

The  heat  exchange  core  is  accessible  through  the 

front service  door.  Special  care  and  attention  should 

be  given  to  this  component  as  the  edges  may  be 

sharp,  and  the  core  itself  susceptible  to  damage  if 

dropped.

When  removing  the  core,  the  location  it  is  removed 

from should be noted.
The  core  is  removed  by  carefully  pulling  the  core 

outward from  the  unit,  sliding  it  evenly  along  its  “H 

channel” supports  found  in  each  corner  of  the  core. 

Note  the  core  may  have  some  resistance  when 

sliding  out.  Avoid  tilting  the  core  as  this  will  result 

in  its  edges  catching  the H channel and temporarily 

preventing its removal.
In  most  cases,  washing  the  core  in  a  mild  detergent 

and  warm  water  will  be  all  that  is  needed  to 

completely  clean them.  Do  not  use  harsh  chemicals 

as  this  may  cause  corrosion  in  the  HRV.  The  time 

between  core  service  will  depend  on  the  application 

the  HRV  has  been  installed  in.  It can  be  as  often  as 

one  -  two  months  or  at  the  very  least, cleaned  every 

six  months.  When  reinstalling  the  core  you  must 

note  foam  location  and  drip  edge  location  for  proper 

core placement. See diagram below.
With the core in its proper position, place the bottom 

flange,(approximately  1/4”)  into  its  H  channel 

support,  then  place the  left  side,  the  right  side  and 

finally  the  top  flange  into place in the same fashion. 

Once  all  four  corners  are  in  place,  push  the  core 

evenly  into  the  cabinet  until  it  reaches  the back. Be 

sure the drip edges are overlapping the drip trays.
Note the core will protrude slightly out from the front 

of  the  cabinet,  this  is  so  the  access  door,  when 

closed, ensures  a tight fit.

SINGLE DRIP

EDGE CORE

FILTER

FILTER

LEFT DRIP

EDGE

DRAIN

PAN

RIGHT DRIP

EDGE

FRONT VIEW

Service

 

and

 

Maintenance

ATTENTION

Do not use cleaning solutions for the HRV

Core

Soak and rinse the HRV core in warm soapy

water

Do not use chlorine or bleach

Do not use a pressure washer on the HRV

core

Do not place he HRV core in the dishwasher

Note: 

When removing cores and filters note their original location and arrangement.

24

Summary of Contents for 350DCS

Page 1: ...door temperatures exceed 15 C 59 F INSTALLER Leave this manual for the homeowner Operation and Installation Manual Commercial Double Core Heat Recovery System Model 350DCS Installation and wiring to b...

Page 2: ...lation careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment i e a forced air furnace or air handler operating at a higher static...

Page 3: ...0 WATTS Low speed 187 WATTS High speed 610 Amp rating 6 3 AIRFLOWS Each Air Stream 250 200 150 100 50 0 1 0 2 100 90 80 300 143 400 190 500 235 600 282 AIRFLOW IN CFM L s NOTE Exhaust Relative Humidit...

Page 4: ...20 minutes ON 40 minutes OFF or 10 minutes ON 50 minutes OFF for even less ventilation Controlling Your HRV Glossary DEFROST MODE to ensure reliable operation during cold weather the HRV will automati...

Page 5: ...ation and increase to high speed during increased activity levels such as cooking and showering etc II 20 Minutes On 40 Minutes Recirculation 20 hr 40 hr This mode ventilates for 20 minutes and recirc...

Page 6: ...or 60 minutes and 4 times to disable The will appear on the screen and the corresponding section of the clock will flash to indicate the time interval selected When the timer runs out the unit will re...

Page 7: ...Humidity Control Your unit will reduce indoor humidity when outdoor humidity levels are lower than indoor humidity levels This feature is only effective when the outdoor temperature is below 59 F 15 C...

Page 8: ...umidity level is lower than the setting Refer to the unit s Home Owner s manual for instructions on how the Dehumidistat works The Dehumidistat will override the current fan speed setting to high fan...

Page 9: ...densation on windows indicates a high level of humidity The amount of condensation on the windows will increase as outdoor temperatures drop Your HRV will reduce indoor humidity levels when outdoor ai...

Page 10: ...is measured at the control Setting the Dehumidistat Press and release the Dehumidistat button until the Dehumidistat Light is at the desired setting After 5 seconds the Dehumidistat light will either...

Page 11: ...02 control drill a 1 in hole in the center Figure D For BC02 BC03 or BC04 controls cut in a 3 4 in by 1 in oval hole in the wall Figure E or F 7 Pull 3 wire 20 gauge min 100 ft length max through the...

Page 12: ...Back Plate Figure C 7 Secure a single wire to the Wire Retainer located on the Back Plate Figure C 8 Attach the Back Plate to the wall using the 2 supplied screws and anchors 9 Attach the Face Plate...

Page 13: ...eater may be installed to increase the range of the Timers Test if pairing was successful by pressing the Select Button and listen for the HRV to initiate HIGH fan speed Ventilation Un pairing 1 Remov...

Page 14: ...ss Timer When paired to the main wall control the Wireless Timer may be moved to a remote location in the home such as a bathroom Pressing the Select Button on the Timer will initiate HIGH speed fan o...

Page 15: ...h Wireless Repeater Part 99 RX02 Operating your Lifebreath 20 40 60 Minute Fan Timer Press and release the Select Button to activate a 20 40 or 60 minute high speed override cycle The High Speed Statu...

Page 16: ...inal Block CAUTION Consideration should be given to competing airflows when connecting the HRV in conjunction with an Air Handler Furnace Blower system Setting Standby when using a Main Control CAUTIO...

Page 17: ...nnel Supplied by others Vibration Isolators Supplied by others Curb Mounted Mount unit on wooden or metal curb assembly Unit must be raised an adequate height for installation and slope of drain lines...

Page 18: ...high quality caulking preferably acoustical sealant and taping with a high quality aluminum foil tape is recommended to seal the duct to both the HRV and the weatherhood A properly designed ducting sy...

Page 19: ...interfaced with the Airhandler Furnace when this system is used refer to Interlocking the HRV to an Airhandler Furnace blower in this manual The HRV exhaust take off connection must be at least 3 ft...

Page 20: ...introduced directly into the ceiling space but this should occur near the air handler s intake In installations where it is satisfactory to provide general exhaust from the space the air to be exhaus...

Page 21: ...t with a zip tie zip tie not included Pour a cup of water into the drain pan of the HRV after the drain connection is complete This creates a water seal that prevents odors from being drawn up the hos...

Page 22: ...unit Drill a small hole in the duct about 3 16 three feet downstream of any elbows or bends and one foot upstream of any elbows or bends These are recommended distances but the actual installation ma...

Page 23: ...atching the H channel and temporarily preventing its removal In most cases washing the core in a mild detergent and warm water will be all that is needed to completely clean them Do not use harsh chem...

Page 24: ...Ensure that the pans drain completely and in a reasonable amount of time Note if the water does not drain right away check for blockage in the drain line also check that the drain line has a good slo...

Page 25: ...Wiring Diagram Model 350DCS 26...

Page 26: ...n Ontario N5W 4C8 519 457 1904 or fax 519 457 1676 to find the name of your nearest dealer in order to repair the product The labour required to install any replacement part s shall be dealt with at t...

Page 27: ...28 info lifebreath com T 1 855 247 4200 F 1 800 494 4185 69 350DCS 072020...

Reviews: