background image

5

Today's modern, tight buildings require fresh outdoor air to 

maintain  a  healthy  indoor  air  environment.  The  amount  of 

ventilation you require in the building will depend upon:

The number of occupants and their activity levels

The way the building was built

Your personal preferences for fresh air

The HRV introduces fresh air to the building while recovering 

energy from the air it exhausts. Specifically, an HRV that is 

properly installed, operated and maintained will:

exhaust stale, contaminated air

recover  the  majority  of  the  energy  from  the

exhausted stale air

use the recovered energy to preheat or precool outside

air that is drawn into the building

distribute the fresh air throughout the building

HOW

 

MUCH

 

VENTILATION

 

DO

 

I

 

NEED?

During  seasons  when  your  windows  and  doors  are  closed 

(winter, and summer if air conditioned), the HRV should  be 

set to operate continuously on low speed with the option of 

going  to  high  speed as the need arises. For example, if you 

are  entertaining  and  there  is  a  large  number  of  people 

present,  the  unit  should  be  switched  temporarily  to  high 

speed.
You  may  wish  to  use  an  intermittent  operational  mode  if 

the  building  is  unoccupied  (20  minutes  ON  /  40  minutes 

OFF  or  10  minutes  ON  /  50  minutes  OFF  for  even  less 

ventilation).

Controlling

 

Your

 

HRV

Glossary

DEFROST  MODE 

-  to  ensure  reliable  operation  during 

cold weather, the HRV will automatically cycle through its 

defrost mode as needed.

DEHUMIDISTAT 

-  a  control  device  that  senses  the 

amount  of  moisture  in  the  air  and  activates  high  speed 

ventilation  when  the  air  moisture  level  in  the  home 

exceeds the set point.

RECIRCULATION

  -  Recirculates  existing  household  air 

without introducing fresh air.

RESET 

-  whenever  resetting  of  the  HRV  is  required, 

disconnect power for 30 seconds. The Self Test will occur 

when the HRV is re reconnected.

SELF  TEST

  -  each  time  the  HRV  is  powered/energized 

the self test function will automatically initiate. During the 

self  test  the  HRV  will  cycle  through  all  the  speeds 

available (1-5), test the damper motor operation and will 

default back to the previous operational mode and speed 

selection.  Total  self  test  duration  is  approximately  90 

seconds.

STANDBY  MODE 

-  the  HRV  is  powered/energized  and 

waiting for fan operation to be initiated. For example, the 

HRV  is  set  a  Continuous  Ventilation  Operational  Mode  at 

Speed 0. 

THERMISTOR 

-  the  HRV's  temperature  sensor  which 

measures  electrical  resistance  in  a  known  manner,  as 

outdoor temperatures fluctuate.

VENTIALTION

  -  Operational  mode  that  introduces  fresh 

outdoor air to the home or building.

Summary of Contents for 350DCS

Page 1: ...door temperatures exceed 15 C 59 F INSTALLER Leave this manual for the homeowner Operation and Installation Manual Commercial Double Core Heat Recovery System Model 350DCS Installation and wiring to b...

Page 2: ...lation careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment i e a forced air furnace or air handler operating at a higher static...

Page 3: ...0 WATTS Low speed 187 WATTS High speed 610 Amp rating 6 3 AIRFLOWS Each Air Stream 250 200 150 100 50 0 1 0 2 100 90 80 300 143 400 190 500 235 600 282 AIRFLOW IN CFM L s NOTE Exhaust Relative Humidit...

Page 4: ...20 minutes ON 40 minutes OFF or 10 minutes ON 50 minutes OFF for even less ventilation Controlling Your HRV Glossary DEFROST MODE to ensure reliable operation during cold weather the HRV will automati...

Page 5: ...ation and increase to high speed during increased activity levels such as cooking and showering etc II 20 Minutes On 40 Minutes Recirculation 20 hr 40 hr This mode ventilates for 20 minutes and recirc...

Page 6: ...or 60 minutes and 4 times to disable The will appear on the screen and the corresponding section of the clock will flash to indicate the time interval selected When the timer runs out the unit will re...

Page 7: ...Humidity Control Your unit will reduce indoor humidity when outdoor humidity levels are lower than indoor humidity levels This feature is only effective when the outdoor temperature is below 59 F 15 C...

Page 8: ...umidity level is lower than the setting Refer to the unit s Home Owner s manual for instructions on how the Dehumidistat works The Dehumidistat will override the current fan speed setting to high fan...

Page 9: ...densation on windows indicates a high level of humidity The amount of condensation on the windows will increase as outdoor temperatures drop Your HRV will reduce indoor humidity levels when outdoor ai...

Page 10: ...is measured at the control Setting the Dehumidistat Press and release the Dehumidistat button until the Dehumidistat Light is at the desired setting After 5 seconds the Dehumidistat light will either...

Page 11: ...02 control drill a 1 in hole in the center Figure D For BC02 BC03 or BC04 controls cut in a 3 4 in by 1 in oval hole in the wall Figure E or F 7 Pull 3 wire 20 gauge min 100 ft length max through the...

Page 12: ...Back Plate Figure C 7 Secure a single wire to the Wire Retainer located on the Back Plate Figure C 8 Attach the Back Plate to the wall using the 2 supplied screws and anchors 9 Attach the Face Plate...

Page 13: ...eater may be installed to increase the range of the Timers Test if pairing was successful by pressing the Select Button and listen for the HRV to initiate HIGH fan speed Ventilation Un pairing 1 Remov...

Page 14: ...ss Timer When paired to the main wall control the Wireless Timer may be moved to a remote location in the home such as a bathroom Pressing the Select Button on the Timer will initiate HIGH speed fan o...

Page 15: ...h Wireless Repeater Part 99 RX02 Operating your Lifebreath 20 40 60 Minute Fan Timer Press and release the Select Button to activate a 20 40 or 60 minute high speed override cycle The High Speed Statu...

Page 16: ...inal Block CAUTION Consideration should be given to competing airflows when connecting the HRV in conjunction with an Air Handler Furnace Blower system Setting Standby when using a Main Control CAUTIO...

Page 17: ...nnel Supplied by others Vibration Isolators Supplied by others Curb Mounted Mount unit on wooden or metal curb assembly Unit must be raised an adequate height for installation and slope of drain lines...

Page 18: ...high quality caulking preferably acoustical sealant and taping with a high quality aluminum foil tape is recommended to seal the duct to both the HRV and the weatherhood A properly designed ducting sy...

Page 19: ...interfaced with the Airhandler Furnace when this system is used refer to Interlocking the HRV to an Airhandler Furnace blower in this manual The HRV exhaust take off connection must be at least 3 ft...

Page 20: ...introduced directly into the ceiling space but this should occur near the air handler s intake In installations where it is satisfactory to provide general exhaust from the space the air to be exhaus...

Page 21: ...t with a zip tie zip tie not included Pour a cup of water into the drain pan of the HRV after the drain connection is complete This creates a water seal that prevents odors from being drawn up the hos...

Page 22: ...unit Drill a small hole in the duct about 3 16 three feet downstream of any elbows or bends and one foot upstream of any elbows or bends These are recommended distances but the actual installation ma...

Page 23: ...atching the H channel and temporarily preventing its removal In most cases washing the core in a mild detergent and warm water will be all that is needed to completely clean them Do not use harsh chem...

Page 24: ...Ensure that the pans drain completely and in a reasonable amount of time Note if the water does not drain right away check for blockage in the drain line also check that the drain line has a good slo...

Page 25: ...Wiring Diagram Model 350DCS 26...

Page 26: ...n Ontario N5W 4C8 519 457 1904 or fax 519 457 1676 to find the name of your nearest dealer in order to repair the product The labour required to install any replacement part s shall be dealt with at t...

Page 27: ...28 info lifebreath com T 1 855 247 4200 F 1 800 494 4185 69 350DCS 072020...

Reviews: