background image

14

Optional Lifebreath Wireless Timer - Part #99-DET02

ATTENTION

The  Wireless  Timers  and  Repeaters  must  be 
matched to  the  main  wall  control  of  the  HRV.  
This  process  is  called  "Pairing".    Multiple 
Timers  and Repeaters can be paired to a single 
wall control.

BC

02, BC03 or 

BC04 Control

NOTE:

  Your BC 

control may look 
different than the 
one shown.

Press Simultaneously to 
Initiate Pairing Mode

Figure A 

Figure B

1/8 in hole for 
screw and 
anchor 

1/8 in hole 
for screw and 
anchor 

Break off tab

Alternate Wall Mount

1/8 in hole for 

screw and anchor 

Figure C

Back Plate 

Face Plate 

1/8 in 
hole for 
screw and 
anchor

Break off tab

Figure E 

Figure D

DET02 Timer

20/40/60 Minute 
Status Lights 

Select Button 

initiates high speed 

ventilation for 20, 40 

or 60 min. 

Battery Indicator

Removable 

Backplate

The 

timer 

will 

override 

the 

operational 

mode 

(regardless  of  the  settings)  and  initiate  HIGH  speed 
Ventilation.  Upon  completion  of  the  timer  cycle,  the  HRV 
will  return  to  your  selected  operational  mode  and  speed 
setting. 
Initiates  HIGH  speed  ventilation  for  20,  40  or  60  minutes.  The 
20/40/60  minute  Status  Lights  indicate  HIGH  speed 
operation. 
The  Wireless  Timers  are  to  be  surface  mounted  onto  a 
wall.  Multiple  Wireless  Timers  may  be  installed  in  a  ventilation 
system.    To  increase  the  range  of  a  Wireless  Timer,  a  RX02 
Repeater should be used.

Pairing:

To  pair  additional  DET02  Timers  with  the  same  wall control, or if  pairing 
was  not  successful,  repeat steps 1-6.
When  paired,  the  DET02  Timers  can  be  moved  and  installed  elsewhere.  
Estimated  range  of  the  Timer  is  40’ with no obstructions.  A RX02 Repeater may 
be installed to increase the range of the Timers.
Test if pairing was successful by pressing the Select Button and  listen  for  the 
HRV  to  initiate  HIGH  fan  speed Ventilation.

Un-pairing: 

1.

Remove the battery from the back of the DET02 Timer

2.

Press  and  hold  the  Select  Button  on  the  front  of  the Timer

3.

While holding the Select Button, reinsert the battery in the Timer.  Continue holding the Select
Button until the LED under "40" begins flashing.  The DET02 Timer will now be unpaired with the
main wall control.

1.

Turn on the main wall control by pressing the ON/OFF

button     and remove the battery from Timer.

2.

DET02 with DX

PL

02

 Controls:

   Press the left and

right buttons simultaneously on the main wall control
(    and RESET buttons).  The screen will go blank and
the wireless symbol     will appear flashing on the
bottom right of the display.  This indicates that the main
control is now in pairing mode.  (Figure D)

3.

DET02 with BC

02, BC03 and BC04

 Controls:

 

Press the left and right buttons simultaneously on the
main wall control

 

(    and either     or      buttons,

depending on the main control).  The bottom row of 3
LED's will begin flashing. This indicates that the main
control is now in pairing mode.(Figure E)

4.

Keep the Timer within 16” of the main wall control when

pairing.

5.

Install the battery in the DET02 Timer.  All four lights on

the Timer will immediately flash 5 times, then only the
red battery light will remain on for approximately 12
seconds after which the "40" light flashes the rev code.
20, 40, 60 lights will flash until paired  or will stop if not
paired within 12 seconds.  If pairing was not successful
you now must return to step 1 to restart the pairing
process.

6.

Press the     button on the main wall control to exit

pairing mode when Timers have been successfully
paired.

Summary of Contents for 350DCS

Page 1: ...door temperatures exceed 15 C 59 F INSTALLER Leave this manual for the homeowner Operation and Installation Manual Commercial Double Core Heat Recovery System Model 350DCS Installation and wiring to b...

Page 2: ...lation careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment i e a forced air furnace or air handler operating at a higher static...

Page 3: ...0 WATTS Low speed 187 WATTS High speed 610 Amp rating 6 3 AIRFLOWS Each Air Stream 250 200 150 100 50 0 1 0 2 100 90 80 300 143 400 190 500 235 600 282 AIRFLOW IN CFM L s NOTE Exhaust Relative Humidit...

Page 4: ...20 minutes ON 40 minutes OFF or 10 minutes ON 50 minutes OFF for even less ventilation Controlling Your HRV Glossary DEFROST MODE to ensure reliable operation during cold weather the HRV will automati...

Page 5: ...ation and increase to high speed during increased activity levels such as cooking and showering etc II 20 Minutes On 40 Minutes Recirculation 20 hr 40 hr This mode ventilates for 20 minutes and recirc...

Page 6: ...or 60 minutes and 4 times to disable The will appear on the screen and the corresponding section of the clock will flash to indicate the time interval selected When the timer runs out the unit will re...

Page 7: ...Humidity Control Your unit will reduce indoor humidity when outdoor humidity levels are lower than indoor humidity levels This feature is only effective when the outdoor temperature is below 59 F 15 C...

Page 8: ...umidity level is lower than the setting Refer to the unit s Home Owner s manual for instructions on how the Dehumidistat works The Dehumidistat will override the current fan speed setting to high fan...

Page 9: ...densation on windows indicates a high level of humidity The amount of condensation on the windows will increase as outdoor temperatures drop Your HRV will reduce indoor humidity levels when outdoor ai...

Page 10: ...is measured at the control Setting the Dehumidistat Press and release the Dehumidistat button until the Dehumidistat Light is at the desired setting After 5 seconds the Dehumidistat light will either...

Page 11: ...02 control drill a 1 in hole in the center Figure D For BC02 BC03 or BC04 controls cut in a 3 4 in by 1 in oval hole in the wall Figure E or F 7 Pull 3 wire 20 gauge min 100 ft length max through the...

Page 12: ...Back Plate Figure C 7 Secure a single wire to the Wire Retainer located on the Back Plate Figure C 8 Attach the Back Plate to the wall using the 2 supplied screws and anchors 9 Attach the Face Plate...

Page 13: ...eater may be installed to increase the range of the Timers Test if pairing was successful by pressing the Select Button and listen for the HRV to initiate HIGH fan speed Ventilation Un pairing 1 Remov...

Page 14: ...ss Timer When paired to the main wall control the Wireless Timer may be moved to a remote location in the home such as a bathroom Pressing the Select Button on the Timer will initiate HIGH speed fan o...

Page 15: ...h Wireless Repeater Part 99 RX02 Operating your Lifebreath 20 40 60 Minute Fan Timer Press and release the Select Button to activate a 20 40 or 60 minute high speed override cycle The High Speed Statu...

Page 16: ...inal Block CAUTION Consideration should be given to competing airflows when connecting the HRV in conjunction with an Air Handler Furnace Blower system Setting Standby when using a Main Control CAUTIO...

Page 17: ...nnel Supplied by others Vibration Isolators Supplied by others Curb Mounted Mount unit on wooden or metal curb assembly Unit must be raised an adequate height for installation and slope of drain lines...

Page 18: ...high quality caulking preferably acoustical sealant and taping with a high quality aluminum foil tape is recommended to seal the duct to both the HRV and the weatherhood A properly designed ducting sy...

Page 19: ...interfaced with the Airhandler Furnace when this system is used refer to Interlocking the HRV to an Airhandler Furnace blower in this manual The HRV exhaust take off connection must be at least 3 ft...

Page 20: ...introduced directly into the ceiling space but this should occur near the air handler s intake In installations where it is satisfactory to provide general exhaust from the space the air to be exhaus...

Page 21: ...t with a zip tie zip tie not included Pour a cup of water into the drain pan of the HRV after the drain connection is complete This creates a water seal that prevents odors from being drawn up the hos...

Page 22: ...unit Drill a small hole in the duct about 3 16 three feet downstream of any elbows or bends and one foot upstream of any elbows or bends These are recommended distances but the actual installation ma...

Page 23: ...atching the H channel and temporarily preventing its removal In most cases washing the core in a mild detergent and warm water will be all that is needed to completely clean them Do not use harsh chem...

Page 24: ...Ensure that the pans drain completely and in a reasonable amount of time Note if the water does not drain right away check for blockage in the drain line also check that the drain line has a good slo...

Page 25: ...Wiring Diagram Model 350DCS 26...

Page 26: ...n Ontario N5W 4C8 519 457 1904 or fax 519 457 1676 to find the name of your nearest dealer in order to repair the product The labour required to install any replacement part s shall be dealt with at t...

Page 27: ...28 info lifebreath com T 1 855 247 4200 F 1 800 494 4185 69 350DCS 072020...

Reviews: