background image

Installation

 

of

 

the

 

Main

 

Control

P

F

12

The 

Lifebreath  Digital  Control  99-DXPL02

  is  to  be  surface  mounted  onto  a  wall  and  the 

Lifebreath  Ventilation 

Controls 99-BC02, 99-BC03 and 99-BC04  

may either be installed onto a flush mounted electrical switch box or surface 

mounted onto  a  wall.  Only  one  master  control should be installed to a ventilation system (the face plate on this illustration 
may not be exactly the same as yours).

1.

For  DXPL

02

 

control

remove 

the

operating  instructions  card  from  the  top
of the  control (Figure A).

2.

Separate  the  face  plate  from  the  back  plate

by  firmly  pulling  apart  (Figures  B  or  C).  Be
careful not to damage face plate contact pins.

3.

For DXPL

02

 control

, place the back plate of

the  control  in  the  desired  location  on  the
wall  and  pencil  mark  the  wall  with  the  right
and  left screw holes (Figure D).

4.

For  BC02,  BC03  or  BC04  controls

,  place

the  back  plate  of  the  control  in  the  desired
location on the wall and pencil mark the top and
bottom screw holes (Figure E or F). For mounting
the control without a Decora plate, break off top
and  bottom  tabs  and  refer  to  Figure  F  for
mounting.

5.

Remove the back plate from the wall and mark

the center hole for the wires in the middle of the
screw  holes.    Refer  to  Figure  D,  E  or  F  for
dimensions.

6.

Drill (two) 1/8 in holes for the screws and wall

anchors  (Figure  D,  E  or  F).   

For  DXPL02

control

,  drill  a  1  in  hole  in  the  center

(Figure  D).    For 

BC02,  BC03  or  BC04

controls

,  cut  in  a  3/4  in  by  1  in  oval  hole  in

the wall (Figure E or F).

7.

Pull  3  wire  20  gauge  (min.)  100  ft  length

(max.), through the opening in the wall.

8.

Connect  red,  green,  and  yellow  to  the  wiring

terminals located on the back plate (Figure D, E
or F).

9.

Attach  the  back  plate  to  the  wall  using  two

supplied screws and anchors.

10.

Attach the face plate to the back plate (Figure

B  or  C).  Note:  Be  careful  to  correctly  align  the
face  plate  to  avoid  damaging  the  face  plate
contact pins.

11.

For  DXPL02  control

,  insert  the  operating

instructions card into the control (Figure A).

12.

Connect  the  3  wire  20  gauge  (min.)  100  ft

length  (max.)  to  the  terminal  block  located  on
ventilator (Red #3, Yellow #4 and Green #5).

Operating

 

Instruction

 

Card

 

Figure A 

Keep top / bottom 

vent openings clear

Figure D

(Two) 1/8 in hole for 

screws and anchors. 

1.5"

1.5"

1 in hole for 

Wiring

wire opening.

Terminals

Face 

Plate 

Figure B 

Back

 

Plate

 

Figure C

Keep top / bottom 

vent openings clear

Back Plate 

Face Plate 

Figure E

1.625"

0.75

"

1.625"

1/8 in hole for 

screw and 

anchor 

1 in x 3/4 in 

for wire 

opening

Wiring

Terminals

1/8 in hole 

for screw and 

anchor 

oval hole 

Break off tab

Alternate Wall Mount

1/8 in hole for 

screw and 

anchor 

1 in x 3/4 in 

0.75

"

oval hole 

1/8 in 

for wire 

hole for 

opening

screw and 

anchor

Wiring

Terminals

Break off tab

Figure F

1

"

Wire hole 

centered 

between  

screw 

holes

ATTENTION

Pay

 

special

 

attention

 

not

 

to

 

damage

 

the

 

Contact

 

Pins

 

when

 

attaching

 

and

 

detaching

 

the

 

Face

 

Plate.  

(Figures

 

B or C)

1

"

Summary of Contents for 350DCS

Page 1: ...door temperatures exceed 15 C 59 F INSTALLER Leave this manual for the homeowner Operation and Installation Manual Commercial Double Core Heat Recovery System Model 350DCS Installation and wiring to b...

Page 2: ...lation careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment i e a forced air furnace or air handler operating at a higher static...

Page 3: ...0 WATTS Low speed 187 WATTS High speed 610 Amp rating 6 3 AIRFLOWS Each Air Stream 250 200 150 100 50 0 1 0 2 100 90 80 300 143 400 190 500 235 600 282 AIRFLOW IN CFM L s NOTE Exhaust Relative Humidit...

Page 4: ...20 minutes ON 40 minutes OFF or 10 minutes ON 50 minutes OFF for even less ventilation Controlling Your HRV Glossary DEFROST MODE to ensure reliable operation during cold weather the HRV will automati...

Page 5: ...ation and increase to high speed during increased activity levels such as cooking and showering etc II 20 Minutes On 40 Minutes Recirculation 20 hr 40 hr This mode ventilates for 20 minutes and recirc...

Page 6: ...or 60 minutes and 4 times to disable The will appear on the screen and the corresponding section of the clock will flash to indicate the time interval selected When the timer runs out the unit will re...

Page 7: ...Humidity Control Your unit will reduce indoor humidity when outdoor humidity levels are lower than indoor humidity levels This feature is only effective when the outdoor temperature is below 59 F 15 C...

Page 8: ...umidity level is lower than the setting Refer to the unit s Home Owner s manual for instructions on how the Dehumidistat works The Dehumidistat will override the current fan speed setting to high fan...

Page 9: ...densation on windows indicates a high level of humidity The amount of condensation on the windows will increase as outdoor temperatures drop Your HRV will reduce indoor humidity levels when outdoor ai...

Page 10: ...is measured at the control Setting the Dehumidistat Press and release the Dehumidistat button until the Dehumidistat Light is at the desired setting After 5 seconds the Dehumidistat light will either...

Page 11: ...02 control drill a 1 in hole in the center Figure D For BC02 BC03 or BC04 controls cut in a 3 4 in by 1 in oval hole in the wall Figure E or F 7 Pull 3 wire 20 gauge min 100 ft length max through the...

Page 12: ...Back Plate Figure C 7 Secure a single wire to the Wire Retainer located on the Back Plate Figure C 8 Attach the Back Plate to the wall using the 2 supplied screws and anchors 9 Attach the Face Plate...

Page 13: ...eater may be installed to increase the range of the Timers Test if pairing was successful by pressing the Select Button and listen for the HRV to initiate HIGH fan speed Ventilation Un pairing 1 Remov...

Page 14: ...ss Timer When paired to the main wall control the Wireless Timer may be moved to a remote location in the home such as a bathroom Pressing the Select Button on the Timer will initiate HIGH speed fan o...

Page 15: ...h Wireless Repeater Part 99 RX02 Operating your Lifebreath 20 40 60 Minute Fan Timer Press and release the Select Button to activate a 20 40 or 60 minute high speed override cycle The High Speed Statu...

Page 16: ...inal Block CAUTION Consideration should be given to competing airflows when connecting the HRV in conjunction with an Air Handler Furnace Blower system Setting Standby when using a Main Control CAUTIO...

Page 17: ...nnel Supplied by others Vibration Isolators Supplied by others Curb Mounted Mount unit on wooden or metal curb assembly Unit must be raised an adequate height for installation and slope of drain lines...

Page 18: ...high quality caulking preferably acoustical sealant and taping with a high quality aluminum foil tape is recommended to seal the duct to both the HRV and the weatherhood A properly designed ducting sy...

Page 19: ...interfaced with the Airhandler Furnace when this system is used refer to Interlocking the HRV to an Airhandler Furnace blower in this manual The HRV exhaust take off connection must be at least 3 ft...

Page 20: ...introduced directly into the ceiling space but this should occur near the air handler s intake In installations where it is satisfactory to provide general exhaust from the space the air to be exhaus...

Page 21: ...t with a zip tie zip tie not included Pour a cup of water into the drain pan of the HRV after the drain connection is complete This creates a water seal that prevents odors from being drawn up the hos...

Page 22: ...unit Drill a small hole in the duct about 3 16 three feet downstream of any elbows or bends and one foot upstream of any elbows or bends These are recommended distances but the actual installation ma...

Page 23: ...atching the H channel and temporarily preventing its removal In most cases washing the core in a mild detergent and warm water will be all that is needed to completely clean them Do not use harsh chem...

Page 24: ...Ensure that the pans drain completely and in a reasonable amount of time Note if the water does not drain right away check for blockage in the drain line also check that the drain line has a good slo...

Page 25: ...Wiring Diagram Model 350DCS 26...

Page 26: ...n Ontario N5W 4C8 519 457 1904 or fax 519 457 1676 to find the name of your nearest dealer in order to repair the product The labour required to install any replacement part s shall be dealt with at t...

Page 27: ...28 info lifebreath com T 1 855 247 4200 F 1 800 494 4185 69 350DCS 072020...

Reviews: