background image

Filters

Open front service door to access the filters located in 

both supply  and  exhaust  air  streams.  Note  to  remove 

and install filters,  it  may  be  easier  to  first remove 

the  core(s). Refer to 

CORE

.

The  filters  are  designed  to  stop  large  particles  from 

entering in  the  core.  The  filters  are  fastened  in  place 

by  a  metal spring  rod.  To  remove  filters  from  core(s) 

simply  pull  the rod  from  one  end,  outward  until  free 

from core  lip, and remove.
Only  use 

cold

  water  with  a  mild  detergent  to  wash 

the filters. Do not 

wring out or 

use harsh chemicals.

The  time  between  filter  service  will  depend 

on  the  application  the  HRV  has  been  installed  in.  It 

can  be  as  often  as  one  -  two  months  or  at  the 

very  least, cleaned every six months.

Condensate Drains

The condensate drain consists of one drain pan, which 

may  collect  water  after  the  HRV  initiates  a  defrost 

cycle, and a drain line to remove the condensate.
Maintenance  on  this  portion  of  the  system  should  be 

done  as  often  as  possible  and  should  not  exceed  six 

months. Note bacterial  growth  in  standing  water  is  a 

major  concern  to  healthy  indoor  air  quality,  and 

should be avoided whenever possible.
To  clean  these  components,  open  the  front  service 

door and flush  the  pans  with  water.  Ensure  that  the 

pans  drain completely and in a reasonable amount of 

time.  Note  if  the  water  does  not  drain  right  away, 

check  for  blockage  in  the  drain  line,  also  check  that 

the  drain  line  has  a  good  slope  to  it.  (1/8  -  1/4”  per 

foot)
The  drain  line  itself  should  have  a  “P”  trap  in  it 

below  the  HRV  which  is  to  be  filled  with  water  to 

prevent  odors  or  gases  from  entering  back  into  the 

unit. 

Duct Work

It  is  a  good  idea  to  inspect  ducting,  outside 

weatherhoods  (wall  caps),  and  grilles  for  blockage 

and  dirt  buildup,  at least every six months.
Outside  weatherhoods  should  be  protected  by  a  bird 

screen  which  can  plug  up  with  debris.  Also,  it  is  a 

good  idea  to  visually  confirm  that  the  fresh  air 

supply  is  free  from  any  sources  of  contamination, 

such  as  other  vented  combustion  equipment  added 

after the fact.

Damper Motor

The  damper  motor,  (if  applicable)  is  a  self  contained 

motor and does not require service. The damper door 

attached  to  the  motor  could  use  a  little  lithium 

grease  on  the  shaft  opposite  the  motor,  where  it 

enters  its  holder,  once  every two - three years.

General Maintenance

As  a  final  step  in  a  routine  maintenance  schedule,  it 

is  a  good  idea  to  confirm  operation  of  the  system, 

checking speed  control  functions  and  remote  control 

operation,  if applicable.
Wipe the inside of the cabinet to remove dust and cob 

webs as needed.
It  is  a  good  idea  to  keep  a  service/maintenance  log 

of  the unit.

Service and Maintenance

25

Summary of Contents for 350DCS

Page 1: ...door temperatures exceed 15 C 59 F INSTALLER Leave this manual for the homeowner Operation and Installation Manual Commercial Double Core Heat Recovery System Model 350DCS Installation and wiring to b...

Page 2: ...lation careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment i e a forced air furnace or air handler operating at a higher static...

Page 3: ...0 WATTS Low speed 187 WATTS High speed 610 Amp rating 6 3 AIRFLOWS Each Air Stream 250 200 150 100 50 0 1 0 2 100 90 80 300 143 400 190 500 235 600 282 AIRFLOW IN CFM L s NOTE Exhaust Relative Humidit...

Page 4: ...20 minutes ON 40 minutes OFF or 10 minutes ON 50 minutes OFF for even less ventilation Controlling Your HRV Glossary DEFROST MODE to ensure reliable operation during cold weather the HRV will automati...

Page 5: ...ation and increase to high speed during increased activity levels such as cooking and showering etc II 20 Minutes On 40 Minutes Recirculation 20 hr 40 hr This mode ventilates for 20 minutes and recirc...

Page 6: ...or 60 minutes and 4 times to disable The will appear on the screen and the corresponding section of the clock will flash to indicate the time interval selected When the timer runs out the unit will re...

Page 7: ...Humidity Control Your unit will reduce indoor humidity when outdoor humidity levels are lower than indoor humidity levels This feature is only effective when the outdoor temperature is below 59 F 15 C...

Page 8: ...umidity level is lower than the setting Refer to the unit s Home Owner s manual for instructions on how the Dehumidistat works The Dehumidistat will override the current fan speed setting to high fan...

Page 9: ...densation on windows indicates a high level of humidity The amount of condensation on the windows will increase as outdoor temperatures drop Your HRV will reduce indoor humidity levels when outdoor ai...

Page 10: ...is measured at the control Setting the Dehumidistat Press and release the Dehumidistat button until the Dehumidistat Light is at the desired setting After 5 seconds the Dehumidistat light will either...

Page 11: ...02 control drill a 1 in hole in the center Figure D For BC02 BC03 or BC04 controls cut in a 3 4 in by 1 in oval hole in the wall Figure E or F 7 Pull 3 wire 20 gauge min 100 ft length max through the...

Page 12: ...Back Plate Figure C 7 Secure a single wire to the Wire Retainer located on the Back Plate Figure C 8 Attach the Back Plate to the wall using the 2 supplied screws and anchors 9 Attach the Face Plate...

Page 13: ...eater may be installed to increase the range of the Timers Test if pairing was successful by pressing the Select Button and listen for the HRV to initiate HIGH fan speed Ventilation Un pairing 1 Remov...

Page 14: ...ss Timer When paired to the main wall control the Wireless Timer may be moved to a remote location in the home such as a bathroom Pressing the Select Button on the Timer will initiate HIGH speed fan o...

Page 15: ...h Wireless Repeater Part 99 RX02 Operating your Lifebreath 20 40 60 Minute Fan Timer Press and release the Select Button to activate a 20 40 or 60 minute high speed override cycle The High Speed Statu...

Page 16: ...inal Block CAUTION Consideration should be given to competing airflows when connecting the HRV in conjunction with an Air Handler Furnace Blower system Setting Standby when using a Main Control CAUTIO...

Page 17: ...nnel Supplied by others Vibration Isolators Supplied by others Curb Mounted Mount unit on wooden or metal curb assembly Unit must be raised an adequate height for installation and slope of drain lines...

Page 18: ...high quality caulking preferably acoustical sealant and taping with a high quality aluminum foil tape is recommended to seal the duct to both the HRV and the weatherhood A properly designed ducting sy...

Page 19: ...interfaced with the Airhandler Furnace when this system is used refer to Interlocking the HRV to an Airhandler Furnace blower in this manual The HRV exhaust take off connection must be at least 3 ft...

Page 20: ...introduced directly into the ceiling space but this should occur near the air handler s intake In installations where it is satisfactory to provide general exhaust from the space the air to be exhaus...

Page 21: ...t with a zip tie zip tie not included Pour a cup of water into the drain pan of the HRV after the drain connection is complete This creates a water seal that prevents odors from being drawn up the hos...

Page 22: ...unit Drill a small hole in the duct about 3 16 three feet downstream of any elbows or bends and one foot upstream of any elbows or bends These are recommended distances but the actual installation ma...

Page 23: ...atching the H channel and temporarily preventing its removal In most cases washing the core in a mild detergent and warm water will be all that is needed to completely clean them Do not use harsh chem...

Page 24: ...Ensure that the pans drain completely and in a reasonable amount of time Note if the water does not drain right away check for blockage in the drain line also check that the drain line has a good slo...

Page 25: ...Wiring Diagram Model 350DCS 26...

Page 26: ...n Ontario N5W 4C8 519 457 1904 or fax 519 457 1676 to find the name of your nearest dealer in order to repair the product The labour required to install any replacement part s shall be dealt with at t...

Page 27: ...28 info lifebreath com T 1 855 247 4200 F 1 800 494 4185 69 350DCS 072020...

Reviews: