background image

The  fresh  air  supply  ductwork  from  the  HRV  may 

be  directly  connected  to  the  return  air  duct  of  the 

forced  air  system.  Check  the  air  flow  balance  of  the 

HRV with the air handler  blower  both  “ON”  and  “OFF” 

to  determine  that  it  does  not  imbalance  the  HRV 

more  than  10%.  Also,  it  is  advisable  to  include  a 

short  length  of  flex  duct  or  other  non-metallic 

connector  in  this  hard  ducted  line  in  order  to  keep 

the  HRV  acoustically  isolated  and  separately 

grounded (electrically) from the airhandler.
It  may  be  necessary  to  install  a  separate  fresh  air 

supply ductwork system if the heating is other than 

forced air.
When  installing  an  HRV,  the  designer  and  installer 

should  be  aware  of  local  codes  that  may  require 

smoke  detectors

and/or firestats in the HVAC or HRV ductwork.
Because  an  HRV  is  designed  to  bring  fresh  air  into 

the  building,  structures  may  require  supply  voltage 

interrupt  when  smoke  or  flame  sensors  are 

triggered,  or  when  a  central  fire  alarm  system  is 

activated.
Supply  air  grilles  may  be  ceiling  or  high  wall 

mounted. Avoid locating incoming fresh air grilles that 

could  cause  a  direct  draft  on  the  occupants  as  the 

incoming  air  may  be  below  room  temperature.  A 

reheat  duct  heater  can  be  installed  to  improve 

occupant comfort.

The  stale  air  return  system  is  used  to  draw  air  from 

the points  in  the  building  where  the  worst  air  quality 

problems occur.  Balancing  dampers  and/or  adjustable 

grilles  are recommended  on  all  return  air  lines  which 

are  used  during  installation  to  help  balance  the 

“draw” from different areas of the building.
Alternatively,  the  stale  air  may  be  drawn  directly 

from  the  return  air  duct.  The  airhandler/furnace 

blower  must  operate  continuously  or  be  interfaced 

with  the  Airhandler/Furnace when this system is used 

(refer  to  “Interlocking  the  HRV  to  an  Airhandler/

Furnace  blower  in  this  manual).  The  HRV  exhaust 

take-off  connection  must  be  at  least  3  ft  (1  m) 

upstream  from  the  HRV  supply  duct  if  both  are 

connected to the same duct run.
A  damper  located  just  prior  to  the  HRV  is  required 

to balance  the  stale  air  exhausted  with  the  fresh  air 

supply entering the building.
Return  air  suction  points  should  be  located  on  the 

opposite side of the room from the fresh air inlet. The 

inlets  may  be  located  in  the  ceiling  or  high  on  the 

walls  and  fitted  with inlet grilles.

Many  commercial  activities  produce  air  contaminants 

in  the  form  of  dusts,  fumes,  mists,  vapors 

and  gases.  Contaminants  should  be  controlled  at 

the  source  so  they  are  not  dispersed  through  the 

building  or  allowed  to  increase  to toxic  concentration 

levels.  The  ventilator  allows  for  economical 

operation  of  the  HVAC  system  while effectively 

removing  contaminants  from  the  space.  In designing 

the  exhaust  portion  of  the  system  the  exhaust grilles 

are  situated  to  remove  the  contaminants  while  not 

allowing  them  to  enter  the  breathing  zone  of  the 

occupants.
For  contaminants  lighter  than  air,  grilles  should  be 

located high  on  the  wall.  If  contaminants  are  heavier 

than  air,  a  lower  placement  of  the  grilles  will  be 

required.  Information  on  a  contaminants  specific 

gravity  and  toxicity  should  be available from chemical 

data sheets.

Stale

 

Air

 

Return

 

System

Fresh

 

Air

 

Supply

 

System

Adjustable

 

Grilles

The  use  of  balancing  dampers  or  adjustable  grilles  as 

supply  air  diffusers  and  air  exhaust  covers  are 

recommended.  TECHGRILLES™  are  round,  efficient, 

sound  absorbing  devices  available  in  4”,  5”,  6”  and 

8”  (100,  125,  150, and 200 mm) models.

Part# 99-EAG4 

4” diameter Techgrille

Part# 99-EAG5 

5” diameter Techgrille

Part# 99-EAG6 

6” diameter Techgrille

Part# 99-EAG8 

8” diameter Techgrille

20

Summary of Contents for 350DCS

Page 1: ...door temperatures exceed 15 C 59 F INSTALLER Leave this manual for the homeowner Operation and Installation Manual Commercial Double Core Heat Recovery System Model 350DCS Installation and wiring to b...

Page 2: ...lation careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment i e a forced air furnace or air handler operating at a higher static...

Page 3: ...0 WATTS Low speed 187 WATTS High speed 610 Amp rating 6 3 AIRFLOWS Each Air Stream 250 200 150 100 50 0 1 0 2 100 90 80 300 143 400 190 500 235 600 282 AIRFLOW IN CFM L s NOTE Exhaust Relative Humidit...

Page 4: ...20 minutes ON 40 minutes OFF or 10 minutes ON 50 minutes OFF for even less ventilation Controlling Your HRV Glossary DEFROST MODE to ensure reliable operation during cold weather the HRV will automati...

Page 5: ...ation and increase to high speed during increased activity levels such as cooking and showering etc II 20 Minutes On 40 Minutes Recirculation 20 hr 40 hr This mode ventilates for 20 minutes and recirc...

Page 6: ...or 60 minutes and 4 times to disable The will appear on the screen and the corresponding section of the clock will flash to indicate the time interval selected When the timer runs out the unit will re...

Page 7: ...Humidity Control Your unit will reduce indoor humidity when outdoor humidity levels are lower than indoor humidity levels This feature is only effective when the outdoor temperature is below 59 F 15 C...

Page 8: ...umidity level is lower than the setting Refer to the unit s Home Owner s manual for instructions on how the Dehumidistat works The Dehumidistat will override the current fan speed setting to high fan...

Page 9: ...densation on windows indicates a high level of humidity The amount of condensation on the windows will increase as outdoor temperatures drop Your HRV will reduce indoor humidity levels when outdoor ai...

Page 10: ...is measured at the control Setting the Dehumidistat Press and release the Dehumidistat button until the Dehumidistat Light is at the desired setting After 5 seconds the Dehumidistat light will either...

Page 11: ...02 control drill a 1 in hole in the center Figure D For BC02 BC03 or BC04 controls cut in a 3 4 in by 1 in oval hole in the wall Figure E or F 7 Pull 3 wire 20 gauge min 100 ft length max through the...

Page 12: ...Back Plate Figure C 7 Secure a single wire to the Wire Retainer located on the Back Plate Figure C 8 Attach the Back Plate to the wall using the 2 supplied screws and anchors 9 Attach the Face Plate...

Page 13: ...eater may be installed to increase the range of the Timers Test if pairing was successful by pressing the Select Button and listen for the HRV to initiate HIGH fan speed Ventilation Un pairing 1 Remov...

Page 14: ...ss Timer When paired to the main wall control the Wireless Timer may be moved to a remote location in the home such as a bathroom Pressing the Select Button on the Timer will initiate HIGH speed fan o...

Page 15: ...h Wireless Repeater Part 99 RX02 Operating your Lifebreath 20 40 60 Minute Fan Timer Press and release the Select Button to activate a 20 40 or 60 minute high speed override cycle The High Speed Statu...

Page 16: ...inal Block CAUTION Consideration should be given to competing airflows when connecting the HRV in conjunction with an Air Handler Furnace Blower system Setting Standby when using a Main Control CAUTIO...

Page 17: ...nnel Supplied by others Vibration Isolators Supplied by others Curb Mounted Mount unit on wooden or metal curb assembly Unit must be raised an adequate height for installation and slope of drain lines...

Page 18: ...high quality caulking preferably acoustical sealant and taping with a high quality aluminum foil tape is recommended to seal the duct to both the HRV and the weatherhood A properly designed ducting sy...

Page 19: ...interfaced with the Airhandler Furnace when this system is used refer to Interlocking the HRV to an Airhandler Furnace blower in this manual The HRV exhaust take off connection must be at least 3 ft...

Page 20: ...introduced directly into the ceiling space but this should occur near the air handler s intake In installations where it is satisfactory to provide general exhaust from the space the air to be exhaus...

Page 21: ...t with a zip tie zip tie not included Pour a cup of water into the drain pan of the HRV after the drain connection is complete This creates a water seal that prevents odors from being drawn up the hos...

Page 22: ...unit Drill a small hole in the duct about 3 16 three feet downstream of any elbows or bends and one foot upstream of any elbows or bends These are recommended distances but the actual installation ma...

Page 23: ...atching the H channel and temporarily preventing its removal In most cases washing the core in a mild detergent and warm water will be all that is needed to completely clean them Do not use harsh chem...

Page 24: ...Ensure that the pans drain completely and in a reasonable amount of time Note if the water does not drain right away check for blockage in the drain line also check that the drain line has a good slo...

Page 25: ...Wiring Diagram Model 350DCS 26...

Page 26: ...n Ontario N5W 4C8 519 457 1904 or fax 519 457 1676 to find the name of your nearest dealer in order to repair the product The labour required to install any replacement part s shall be dealt with at t...

Page 27: ...28 info lifebreath com T 1 855 247 4200 F 1 800 494 4185 69 350DCS 072020...

Reviews: