THE INDOOR UNIT INSTALLATION
39
ENGLISH
Mounting the anchor nut and
bolt
- Prepare 4 suspension bolts. (Each bolts
length should be same.)
- Measure and mark the position for the
Suspension bolts and the piping hole.
- Drill the hole for anchor nut on the ceiling.
- Insert the nuts and washer onto the
suspension bolts for locking the suspension
bolts on the ceiling.
- Mount the suspension bolts to the
anchornuts firmly.
- Secure the hangers onto the Suspension
bolts (adjust level roughly.) using nuts,
washers and spring washers.
- Adjust a level with a level gauge on the
direction of left-right, back-forth by adjusting
suspension bolts.
- Adjust a level on the direction of top-bottom
by adjusting suspension bolts. Then the unit
will be declined to the bottomside so as to
drain well.
(Unit : mm)
t
B
A
Nut
Ceiling
Anchor nut
Washer
Washer
Washer
Suspension
Suspension
bolts
bolts
Suspension
bolts
Spring
washer
Max.
12 mm
Nut
Suspension
bolts
Hangen
Washer
Suspension bol
Suspension bol
Suspension bol
Model (kBtu/h)
A
B
18 k/24 k
1 018
355
36 k/42 k/48 k/60 k
1 418
Installation information for declination
- Install declination of the indoor unit is
very important for the drain of the
convertible type air conditioner.
- Minimum thickness of the insulation
for the connecting pipe shall be 10
mm.
- If the Installation Plates are fixed to
horizontal line, the indoor unit after
installing will be declined to the
bottomside.
CAUTION
!