67
INSTALLATION OF INDOOR UNIT
ENGLISH
Table 3 - Minimum venting opening area for natural ventilation
A
room
(m
2
)
Minimum opening area AV
min
(cm
2
)
(Based on h
0
1.3 m)
Total Ref. Amount m
c
(kg)
2.7
2.6
2.5
2.4
2.3
2.2
2.1
2.0
1.9
1
660
632
605
577
550
522
495
467
440
2
578
550
523
495
468
440
413
385
358
3
495
468
440
413
385
358
330
303
275
4
413
386
358
331
303
276
248
221
193
5
331
303
276
248
221
193
166
138
111
6
248
221
193
166
139
111
84
56
29
7
209
180
152
123
95
67
38
10
8
176
147
117
88
58
29
9
143
112
82
52
22
10
109
78
47
16
11
75
43
12
12
41
9
13
7
NOTE
- The value of "Installation height (h
0
)“ in this unit is considered 1 300 mm to comply to IEC
60335-2-40:2013 A1 2016 Clause GG2.
- For intermediate A
room A
values, the value that corresponds to the lower A
room A
value from
the table is considered.
(If A
room A
= 10.5 m
2
, consider the value that corresponds to A
room A
= 10 m
2
.)
- For intermediate m
c
values, the value that corresponds to the higher m
c
value from the table
is considered. (If m
c
= 2.15 kg, the value that corresponds to m
c
= 2.2 kg is considered.)