210
INSTALLER SETTING
ENGLISH
Mixing Circuit
Function to set whether or not to use a installed 2nd circuit function using mixing kit.
You can set valve closing time[s] and hysteresis temperature[°C] on screen by yourself.
Setting the cut-off temperature protects the water from flowing over the cut-off temperature in
the mixing circuit during heating operation.
Installer setting function to set water mixing pump operation / delay time option in
heating/cooling mode
Activating this function, It allows 2 zones(Room1, Room2) temperature to be controlled,
separately.
Setting range
- Mixing Circuit (2nd Circuit function setting) : Not Use / Heat / Heat & Cool
- Value Closing Time : 60 ~ 999 s (Default: 240)
- Hysteresis (Thermal On / Off ) : 1~3 °C (Default: 2)
NOTE
When using the Mixing Circuit function, the external pump setting must be changed to
'Circuit 1'.