236
INSTALLER SETTING
ENGLISH
Function
Description
Range
Default
(Circuit1)
Default
(Circuit2)
Boundary
Outdoor1,Heat
(Out1)
Heating lower ambient
temp
-25 ~ 35 °C
-10 °C
Out1
≤
Out2-1
Outdoor2,Heat
(Out2)
Heating higher ambient
temp
18 °C
Out2
≥
Out1 +1
Out2
≤
Out3 -5
Outdoor3,Cool
(Out3)
Cooling lower ambient
temp
10 ~ 46 °C
30 °C
Out3
≥
Out2 +5
Out3
≤
Out4 -1
Outdoor4,Cool
(Out4)
Cooling higher ambient
temp
40 °C
Out4
≥
Out3 +1
Water1,Heat
(LW1)
Heating higher water
temp
Use heater :
LW STD : 15~65 °C
EW STD : 15~55 °C
Not use heater :
LW STD : 20~65 °C
EW STD : 20~55 °C
50 °C
35 °C
LW1
≥
LW2
Water 2,Heat
(LW2)
Heating lower water
temp
40 °C
28 °C
LW1
≥
LW2
Water3,Cool
(LW3)
Cooling higher water
temp
Use FCU & 5 °C
IDU :
LW STD : 5~27 °C
EW STD : 10~27 °C
Use FCU & 6 °C
IDU :
LW STD : 6~27 °C
EW STD : 11~27 °C
Not use FCU :
LW STD : 16~27 °C
EW STD : 20~27 °C
12 °C
18 °C
LW3
≥
LW4
Water4,Cool
(LW4)
Cooling lower water
temp
10 °C
16 °C
LW3
≥
LW4
Air 1, Heat (RA1) Heating higher air temp
16 ~ 30 °C
21 °C
RA1
≥
RA2
Air 2, Heat (RA2) Heating lower air temp
19 °C
RA1
≥
RA2
Air 3, Cool (RA3) Cooling higher air temp
18 ~ 30 °C
21 °C
RA3
≥
RA4
Air 4, Cool (RA4) Cooling lower air temp
19 °C
RA3
≥
RA4