66
INSTALLATION OF INDOOR UNIT
ENGLISH
Table 2 - Minimum floor area
Total Ref.
+ Amount m
c
(kg)
Minimum Floor Area
A
min
(m
2
)
Based on h
0
1.3 m
1.84
6.15
1.86
6.27
1.88
6.41
1.90
6.54
1.92
6.68
1.94
6.82
1.96
6.96
1.98
7.11
2.00
7.25
2.02
7.40
2.04
7.54
2.06
7.69
2.08
7.84
2.10
8.00
2.12
8.15
2.14
8.30
2.16
8.46
2.18
8.62
2.20
8.77
2.22
8.93
2.24
9.10
2.26
9.26
2.28
9.42
2.30
9.59
2.32
9.76
2.34
9.93
2.36
10.10
2.38
10.27
2.40
10.44
2.42
10.62
2.44
10.79
2.46
10.97
2.48
11.15
2.50
11.33
2.52
11.51
2.54
11.70
2.56
11.88
2.58
12.07
2.60
12.26
2.62
12.44
2.64
12.64
2.66
12.83
2.68
13.02
2.70
13.22
NOTE
- The value of "Installation height (h
0
)“ in
this unit is considered 1 300 mm to
comply to IEC 60335-2-40:2013 A1
2016 Clause GG2.
- For intermediate m
c
values, the value
that corresponds to the higher mc value
from the table is considered. (If m
c
=
1.85 kg, the value that corresponds to
m
c
= 1.86 kg is considered.)
- Systems with total refrigerant charge
lower than 1.84 kg are not subjected to
any room area requirements.
- Charges above 2.70 kg are not allowed
in the unit.
20
A
min
(m
2
)
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
1.5
2.0
m
c
(kg)
3.0
2.5