OPERATION INSTRUCTION
19
ENGLISH
Standard Operation - Timed Override
Timed override operation temporarily changes the occupied/unoccupied schedule for override
time.
- It reverts to the last occupied schedule in unoccupied override.
- It reverts to the last unoccupied schedule in occupied override.
- You can set ‘Override time’ by ‘Function setting – Override set time’
Press button for 3 seconds, you
can operate timed override.
1
Operate Timed override
Cancel Timed override
Press button for 3 seconds in Timed
override mode, you can cancel Timed
override.
- It reverts to the last weekly reservation schedule.
• It reverts to the default operation setting if the Thermostat does not have the last occu-
pied schedule in unoccupied override.
- The default operation setting is Auto operation mode with 86 °F (30 °C) for the cool set
point and 60 °F (16 °C) for the heat set point.
• It reverts to set back operation setting if Thermostat does not have last unoccupied sched-
ule in occupied override.
- Set back operation setting: Auto operation mode / set back setting temperature: function
setting – set back temperature.
• It can be canceled if the Thermostat receives a command from another controller.
• When changes occur in the setting by a daytime reservation operation, the schedule over-
ride mode gets deactivated.