20
OPERATION INSTRUCTION
ENGLISH
Standard Operation - Set back
Set back operation reverts to the last unoccupied schedule until Set back operation is canceled.
• It changes to ‘function setting - set back setting’ if Thermostat doesn’t have last unoccupied
schedule.
- Set back operation setting :
Auto operation mode / Set back setting temperature: Function setting – Set back temperature
Operate set back mode
Cancel set back mode
Press button in set back mode, you will
cancel set back operation.
- It reverts to the last weekly reservation schedule.
Press button, you can operate set back
mode.
• You cannot change the setting in set back mode, except to cancel the set back mode.
- ‘HL’ lock is displayed on the window.
• It can be canceled if the Thermostat receives command from another controller.
• When the set back mode is deactivated, the following take place:
- The set points will go to the current occupied set points.
- The default occupied setting will be Auto with 86 °F (30 °C) for the cool set point and
60 °F (16 °C) for the heat set point.