Refrigerant piping installation
u
Y branch method
Refrigerant piping system
Installation Manual
25
• * : Assume equivalent pipe length of Y branch to be 0.5m, that of header to be 1m, calculation purpose
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Indoor Units
L100m
l
30m
H 10m
h 5m
Ú
Total pipe length = A+B+C+D+a+b+c+d+e ≤ 150m(175m)
Longest pipe length * Equivalent pipe length
A+B+C+D+e ≤ 100m A+B+C+D+e ≤ 125m
Longest pipe length after 1st branch
B+C+D+e ≤ 30m
Difference in height(Outdoor Unit
÷
Indoor Unit)
H ≤ 10m
Difference in height (Indoor Unit
÷
Indoor Unit)
h ≤ 5m
L
l
H
h
ENGLISH