Installation Manual
65
Test Run
Outdoor Unit Fan First Position Sensing Failure
Communication Fail Between Outdoor Unit Main
MICOM and EEPROM or omitting EEPROM
Communication Fail Between Outdoor Unit Fan
MICOM and EEPROM or omitting EEPROM
Faulty communication between PFC MICOM and EEP-
ROM of the outdoor unit or missing EEPROM
Failing to receive fan signal at main PCB of unit.
Instant Over Current at Outdoor Unit Fan IPM.
Outdoor Unit Fan DC Link Input Voltage is under 380V.
Liquid pipe temperature sensor of outdoor unit is open
or short.
Outdoor Unit Subcooling Outlet Temperature Sensor
open or short.
Temperature of inverter board radiator of the outdoor
unit higher than 130°C.
Disconnection or short circuit on temperature sensor of
inverter board radiator of the outdoor unit.
Outdoor Unit Fan Inverter PCB Temperature is Over
95°C
Outdoor Unit Fan PCB Heat Sink Temperature Sensor
open or short.
Network Error of the central control unit.
Outdoor Unit Fan Start Failure
Error
Outdoor Unit Main PCB EEPROM
Error
Outdoor Unit Fan PCB EEPROM
Error
PFC PCB EEPROM Error
Outdoor Unit Fan PCB
Communication Error
Outdoor Unit FAN IPM Fault Error
Outdoor Unit Fan DC Link Low
Voltage Error
Outdoor Unit Liquid pipe
Temperature Sensor Error
Outdoor Unit Subcooling Outlet
Temperature Sensor Error
Overheating of inverter board radi-
ator of the outdoor unit
Error in temperature sensor of
inverter board radiator of the out-
door unit
Excessive increase of Outdoor
Unit Fan PCB Heat Sink
Temperature
Outdoor Unit Fan PCB Heat Sink
Temperature Sensor Error
Network Error
Display Title Cause of Error
1 0 6 1
1 0 7 1
1 1 3 1
1 1 5 1
1 9 0 1
1 9 1 1
1 9 3 1
1 9 4 1
2 4 2 1
Outdoor unit related error
7 9 1
8 6 1
8 7 1
8 8 1
1 0 5 1
ENGLISH