12
Outdoor Unit
Outdoor
A
E
B
D
A
C
B
D
E
C
A
E
C
D
D
D
A
E
B
A
B
E
a
B
Category
4 sides
are walls
2 sides or
1 side are
walls
In case of
Waterproof
wall
installation
Front side : outdoor unit discharge flow direction
Required side area for Louver vane operation should be considered separately.
Installation Space
Side Space
Front
Front
Front
Front
Front
Front
Front
Front
Back
Front
No limit to the
height of the wall
No limit to the
height of the wall
[Unit : mm]
A ≥ 10
B ≥ 500
C ≥ 10
D:Waterproof wall installation condition
A ≥ 10
B ≥ 500
C ≥ 10
D:Waterproof wall installation condition
E ≥ 20
A ≥ 10
B ≥ 500
C ≥ 10
D:Waterproof wall installation condition
E ≥ 20
A ≥ 10
B ≥ 500
A ≥ 10
B ≥ 500
E ≥ 20
If a ≤ 300, D ≥ 150
If 300 < a ≤ 500, D ≥ 250
Installation Space
• The following values are the least space for installation. If any service area si needed for service according to
field circumstance, obtain enough service space.
• The unit of values is mm.