Refrigerant piping installation
u
Combination of Y branch/header method
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Header
Ⓕ
: Sealed piping
L100m
30m
H 10m
h 5m
Branch pipe can not be used after header
Ú
Total pipe length = A+B+C+a+b+c+d+e ≤ 150m(175m)
• * : Assume equivalent pipe length of Y branch to be 0.5m, that of header to be 1m, calculation purpose
Longest pipe length * Equivalent pipe length
A+B+b ≤ 100m A+B+b ≤ 125m
Longest pipe length after 1st branch
B+b ≤ 30m
Difference in height(Outdoor Unit
÷
Indoor Unit)
H ≤ 10m
Difference in height (Indoor Unit
÷
Indoor Unit)
h ≤ 5m
L
l
H
h
Ú
Refrigerant pipe diameter from branch to branch (B,C,D)
Downward Indoor Unit total capacity
[kW(Btu/h)]
≤ 5.6(19,100) Ø6.35(1/4) Ø12.7(1/2)
< 16(54,600) Ø9.52(3/8) Ø15.88(5/8)
≤ 22.4(76,400) Ø9.52(3/8) Ø19.05(3/4)
< 33(112,600) Ø9.52(3/8) Ø22.2(7/8)
Liquid pipe
[mm(inch)]
Gas pipe
[mm(inch)]
Installation Manual
27
ENGLISH