Refrigerant piping installation
u
Header Method
• * : Assume equivalent pipe length of Y branch to be 0.5m, that of header to be 1m, calculation purpose
Example : 6 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch
Ⓒ
: Indoor Units
Ⓓ
: Sealed piping
L 100m
30m
H 10m
h 5m
Branch pipe can not be used after header
Ú
Total pipe length = A+a+b+c+d+e+f ≤ 150m(175m)
Longest pipe length * Equivalent pipe length
A+f ≤ 100m A+f ≤ 125m
Longest pipe length after 1st branch
f ≤ 30m
Difference in height(Outdoor Unit
÷
Indoor Unit)
H ≤ 10m
Difference in height (Indoor Unit
÷
Indoor Unit)
h ≤ 5m
L
l
H
h
26
Outdoor Unit
Pipe length after header branching (a~f)
It is recommended that difference in length of the pipes connected to the Indoor Units is minimized.
Performance difference between Indoor Units may occur.
WARNING