54 | LIMITS / PLACEMENT
MUL
TI V S Three-Phase Outdoor Unit Engineering Manual
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©
/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
THREE-PHASE
• Installation clearances must comply with local building codes.
• All figures not to scale.
Figure 28: Proper Outdoor Unit Placement and Clearances, continued.
Figure 29: Proper Outdoor Unit Placement and Clearances, continued.
Max. 20"
Min. 40"
Min. 40"
Min. 4"
Min. 8"
Min. 14"
L > H
Side by Side—High Rear and Side
Walls with Building Overhang
Side by Side—High Rear and Front Walls
with Building Overhang
Air
flow
Air
flow
Max. 20"
L
H
Min. 50"
Min. 40"
Min. 4"
Min. 14"
Min. 59"
Min. 14"
Min 4"
Min. 40"
Min. 28"
Max. 20"
Min. 4"
Min. 40"
Min. 14"
Min 4"
L
H
Min. 59"
Min. 14"
Min 4"
Min. 40"
Max. 20"
Side by Side —High Front Wall with Building Overhang
and No Side or Rear Walls
Side by Side—High Rear Wall and Low Front Wall with No Side Walls
Side by Side—High Front and Rear Walls with No Side Walls
Side by Side—High Rear Wall and Low Front Wall with Building
Overhang and No Side Walls
Airfl
ow
Airfl
ow
Airfl
ow
Airflo
w
L
H
L > H
L
H
L
H
Min. 4"
Min. 8"
Min. 40"
Min. 14"
Side by Side—High Rear and Side Walls
Airfl
ow
Min. 28"
Min 4"
Side by Side—High Front Wall with No Side Walls
Airfl
ow
L
H
4" Min.
79" Min.
8" Min.
40" Min.
L
12" Min.
119" Min.
H
24" Min.
60" Min.
4" Min.
/
H
One Row of Single Units
Rows of Multiple Units
OUTDOOR UNIT CLEARANCE
REQUIREMENTS