ELECTRICAL CONNECTIONS | 47
Electrical Connections
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©
/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
THREE-PHASE
Generation 4 Indoor Units
LG’s indoor units are designated Generation 4 (Gen 4). For Gen 4 indoor units to operate with
Gen 4 indoor unit features, the air conditioning system must meet the following requirements:
• All indoor units and the air unit must be Gen 4 or higher.
• The air unit must have Gen 4 or higher software factory or field installed.
• Air unit DIP switch 3 must be set to ON (factory default setting is OFF).
• All controllers must support Gen 4 indoor unit features.
The figure at right shows the outdoor unit DIP switch. The air unit, indoor units, and controllers
in a system must be Gen 4 compatible or the system will not operate with Gen 4 indoor unit
features.
Figure 19: Location and Setting of Multi V S
Three-Phase Outdoor Unit DIP Switch 3.
IDU-A
IDU-B
5A 6B
5A 6B
5A 6B
3A 4B
3A 4B
3A 4B
ELECTRICAL CONNECTIONS
Figure 18: Multi V Three-Phase ARUN072BSS5 / ARUN096BSS5 for Heat Pump Operation (Daisy-Chain Power Wiring / Communications Cable
Example).
• Ground wiring is required to prevent accidental electrical shock during current leakage.
Do not connect the ground line to the pipes. There
LVULVNRI¿UHHOHFWULFVKRFNH[SORVLRQSK\VLFDOLQMXU\RUGHDWK
•
,QVWDOODPDLQVKXWRIIVZLWFKWKDWLQWHUUXSWVDOOSRZHUVRXUFHVVLPXOWDQHRXVO\7KHUHLVULVNRI¿UHHOHFWULFVKRFNH[SORVLRQSK\VLFDOLQMXU\RUGHDWK
• Communication cable between outdoor unit to indoor units must be 18 AWG, 2-conductor, twisted, stranded, shielded. Ensure the commu-
nication cable shield is properly grounded to the outdoor unit chassis only. Do not ground the outdoor unit to indoor units communication
cable at any other point. Wiring must comply with all applicable local and national codes. Inadequate connections will generate heat, cause
a fire, and physical injury or death.
• The GND terminal at the main PCB is a negative terminal for dry contact, not a ground. Inadequate connections will generate heat, cause a
fire, and physical injury or death.
• Ground wiring is required to prevent communication problems from electrical noise and motor current leakage.
• Maintain polarity throughout the communication network. The system will malfunction if not properly wired.
• If the system operates in reversed phase, it will break the compressors and other components.
• If there is a possibility of reversed phase, phase loss, momentary blackout, or the power goes on and off while the system is operating, install
D¿HOGVXSSOLHGSKDVHORVVSURWHFWLRQFLUFXLW2SHUDWLQJWKHV\VWHPLQUHYHUVHSKDVHZLOOEUHDNWKHFRPSUHVVRUDQGRWKHUXQLWFRPSRQHQWV
1 2
7
6
5
4
3
1 2
7
6
5
4
3
ON
OFF
1 2
7
6
5
4
3
1 2
7
6
5
4
3
ON
OFF
Multi V S Three-Phase DIP Switch No. 3