Table 2: 208-230V, 60Hz, 3-Phase Outdoor Unit Electrical Data.
Nominal Tons
Unit Model No.
Compressor Motor
Outdoor Unit Fan Motor
MCA
MOCP
Quantity
Motor Amps
Fan Qty.
Amps
RLA (Ea.)
FLA x Qty.
6.0
ARUN072BSS5
1
17.6
2
1.2 x 2
24.4
40
8.0
ARUN096BSS5
1
18.6
2
1.2 x 2
25.7
40
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOCP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size. RFA = Recommended Fuse Amps.
*SCCR rating: 5kA RMS Symmetrical.