OUTDOOR UNITS INFORMATION
9
ENGLISH
Power Supply : 380V, 60Hz / 380 – 415V, 50Hz
CAUTION
!
* JRUN220LTE5 (Single Unit) model can guarantee the operation only within 160%
combination ratio.
Notes :
1) We can guarantee the operation only within 130% combination ratio.
If you want to connect more than 130% combination ratio, please contact us and
discuss the requirement.
2) In case that operating indoor units ratio to rated capacity of outdoor unit is more than
130%, the airflow should be operated as low step in the all indoor units.
3) In case of Space Saving Model (JRUN***LTE5), we can recommend the operation
within 120% combination ration for two or more combination.
4) The numbers in parentheses means maximum connectable indoor units in accordance
with outdoor units combination.
Combination Ratio(50~200%)
Number of Outdoor units
Combination Ratio
Standard Model
Space Saving Model
Single Unit
200%
160%*
Two Units Combination
160%
120%
Three or More Units Combination
130%
120%
Unit
System(HP)
Model
Combination Unit
Independent Unit
Refrigerant Precharged
Amount
kg
lbs
Number of maximum connectable indoor units
Net Weight
kg
lbs
Dimensions (WxHxD)
mm
inch
(36-7/32 × 66-5/32 ×
29-29/32) × 1
(36-7/32 × 66-5/32 ×
29-29/32) × 1
(36-7/32 × 66-5/32 ×
29-29/32) × 1
(36-7/32 × 66-5/32 ×
29-29/32) × 1
Piping Connections
mm(inch)
mm(inch)
1 Outdoor Unit
8
10
12
14
5.0
5.0
5.0
6.6
11.0
11.0
11.0
14.6
13(20)
16(25)
20(30)
23(35)
175 × 1
175 × 1
180× 1
190 × 1
386× 1
386× 1
397 × 1
419 × 1
(920 × 1,680 × 760) × 1 (920 × 1,680 × 760) × 1 (920 × 1,680 × 760) × 1 (920 × 1,680 × 760) × 1
Ø 9.52(3/8)
Ø 9.52(3/8)
Ø 12.7(1/2)
Ø 12.7(1/2)
Ø 19.05(3/4)
Ø 22.2(7/8)
Ø 28.58(1-1/8)
Ø 28.58(1-1/8)
Standard Model
OUTDOOR UNITS INFORMATION
Model Name: JRUN***LTE5
JRUN080LTE5
JRUN080LTE5
JRUN100LTE5
JRUN100LTE5
JRUN120LTE5
JRUN120LTE5
JRUN140LTE5
JRUN140LTE5