56
ELECTRICAL WIRING
ENGLISH
Field Wiring
Single outdoor unit
R S T N
Switch
Fuse
L
N
Communication cable
(2-Wires Cable)
Power cable
(4-Wires Cable)
Communication cable
(3-Wires Cable)
Power cable
(2-Wires Cable)
Power cable
(2-Wires Cable)
Power cable
(2-Wires Cable)
Power cable
(2-Wires Cable)
Power cable
(2-Wires Cable)
[Outdoor Unit]
[Indoor Units]
Outdoor
Power supply
3Ø 4-wire
Indoor
Power supply
(1
Ø
2-wire)
(Main Switch)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
3
4
3
4
3
4
Master
Outdoor
Unit
SODU.B SODU.A
IDU.B
IDU.A
CEN.B
CEN.A
DRY1
DRY2
GND
12V
[Heat Pump]
Between Indoor and Master Outdoor unit
The GND terminal at the main PCB is a ‘-’
terminal for day contact, it is not the point to
make ground connection.
WARNING
!
• Indoor Unit ground wires are required for preventing electrical shock accident during current
leakage, Communication disorder by noise effect and motor current leakage (without
connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately
from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because
this system consists of the equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power
goes on and off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Frequency
Voltage range(V)
Outdoor
Indoor
60 Hz
380 V
220 V
50 Hz
380-415 V 220-240 V