PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
31
ENGLISH
Y branch method
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Indoor Units
Ⓓ
: Downward Indoor Unit
10 m or
less
L165 m
l
40 m (90 m : Conditional application)
H 90 m
Slave2
Slave3
Slave1
Master
G
ODU Capacity
Master ≥ Slave1 ≥ Slave 2 ≥ Slave 3
h 30 m
h1
Series Outdoor Units (2 Units ~ 4 Units)
Combination of Y branch/header Method
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch(Y branch)
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Connection branch pipe between
Outdoor units : ARCNN41
Ⓕ
: Connection branch pipe between
Outdoor units : ARCNN31
Ⓖ
: Connection branch pipe between
Outdoor units : ARCNN21
Ⓗ
: Header
Ⓘ
: Sealing
10 m or
less
H 90 m
G F
E
G F
E
L 165 m
l
40 m(90 m : Conditional application)
ODU Capacity
Master ≥ Slave1 ≥ Slave2 ≥ Slave3
30 m
Master
Slave3
Slave1
Slave2
h1
Header Method
Ⓐ
: Outdoor Unit
Ⓑ
: Header branch
Ⓒ
: Indoor Units
Ⓓ
: Sealing
Ⓔ
: Connection branch pipe between
Outdoor units : ARCNN41
Ⓕ
: Connection branch pipe between
Outdoor units : ARCNN31
Ⓖ
: Connection branch pipe between
Outdoor units : ARCNN21
10 m or
less
H 90 m
L 165 m
40 m
Master
Slave3
Slave1
Slave2
ODU Capacity
Master ≥ Slave1 ≥ Slave2 ≥ Slave3
30 m
GG
h1
F
E
F
E
Ⓔ
: Connection branch pipe between
Outdoor units : ARCNN41
Ⓕ
: Connection branch pipe between
Outdoor units : ARCNN31
Ⓖ
: Connection branch pipe between
Outdoor units : ARCNN21