Individual Installation
During the installation of the unit, consider service, inlet, and outlet and acquire the minimum
space as shown in the figures below.
Category
Installation Space
Case 1
(10 mm
≤
Side Space
≤
49 mm)
Case 2
(Side Space
≥
49 mm)
4 sides
are walls
Only 2
sides are
walls
Limitation
s on the
height of
the wall
(Refer to
4 side
walls)
A
C
B
D
Front
A
E
B
D
Front
E
C
A
E
B
F
C
D
Front
Front
A
E
B
F
C
D
Front
A
B
Front
No limit to the height of the wall
A
E
B
E
Front
No limit to the height of the wall
240 or
more
50 or more
45° or
more
h2
h1
1500
A
B
500
• The height of the wall on the front side must be 1500mm or less.
• The height of the wall on the inlet side must be 500mm or less.
• There is no limit to the wall on the side.
• If the height of the walls on the front and the side are higher than the limit,
there must be additional space on the front and the side.
- Additional Space on the front side by 1/2 of h1.
- Additional Space on the inlet side by 1/2 of h2
- h1 = A(Actual height) - 1500
- h2 = B(Actual height) - 500
A
≥
10
A
≥
50
B
≥
300
B
≥
100
C
≥
10
C
≥
50
D
≥
500
D
≥
500
A
≥
10
A
≥
50
B
≥
300
B
≥
100
C
≥
10
C
≥
50
D
≥
500
D
≥
500
E
≥
20
E
≥
100
A
≥
10
A
≥
50
B
≥
300
B
≥
100
C
≥
10
C
≥
50
D
≥
500
D
≥
500
E
≥
20
E
≥
100
F
≥
600
F
≥
500
A
≥
10
A
≥
50
B
≥
300
B
≥
100
C
≥
10
C
≥
50
D
≥
300
D
≥
100
E
≥
20
E
≥
100
F
≥
500
F
≥
500
A
≥
10
B
≥
300
A
≥
200
B
≥
300
E
≥
400
16
INSTALLATION SPACE
ENGLISH
INSTALLATION SPACE