INTRODUCTION | 9
Introduction
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Multi V S System R410A Refrigerant Charge Calculator (lbs.)
REFRIGERANT CHARGE WORKSHEET
1
CF (Ref.) = Correction Factor for Refrigerant Charge.
2
For refrigerant charge purposes, consider only the liquid line; ignore the vapor line(s).
System Tag or ID:
Job Name: __________________________________________
Project Manager: ____________________________________ Date: ______________
Line #
Description
Chassis I.D.
Size
Quantity CF (Ref.)
1
Total (lbs.)
1
Linear feet of 1/4" liquid line tubing
2
—
—
0.015
2
Linear feet of 3/8" liquid line tubing
2
—
—
0.041
3
Linear feet of 1/2" liquid line tubing
2
—
—
0.079
4
Linear feet of 5/8" liquid line tubing
2
—
—
0.116
5
Linear feet of 3/4" liquid line tubing
2
—
—
0.179
6
Linear feet of 7/8" liquid line tubing
2
—
—
0.238
7
Linear feet of 1" liquid line tubing
2
—
—
0.323
8
St Art Cool Mirror
SJ, SK
5k to 15k
0.53
9
St Art Cool Mirror
SJ, SK
18k to 24k
0.62
10 Standard
SV
30k to 36k
1.01
11 Art Cool Gallery
SF
9k to 12k
0.22
12 1-Way Cassette
TU
7k to 12k
0.44
13 1-Way Cassette
TT
18k to 24k
0.64
14 2-Way Cassette
TS
18k to 24k
0.75
15 4-Way 2' x 2' Cassette
TR
5k to 7k
0.40
16 4-Way 2' x 2' Cassette
TR
9k to 12k
0.55
17 4-Way 2' x 2' Cassette
TQ
15k to 18k
0.71
18 4-Way 3' x 3' Cassette
TN
7k to 24k
0.88
19 4-Way 3' x 3' Cassette
TM
28k to 36k
1.08
20 4-Way 3’ x 3’ Cassette
TM
42k to 48k
1.41
21 High Static Ducted
BH
7k to 24k
0.57
22 High Static Ducted
M2
7k to 24k
0.77
23 High Static Ducted
M2
28k to 42k
1.15
24 High Static Ducted
M3
28k to 54k
1.35
25 High Static Ducted
B8
36k to 96k
2.20
26 Low Static Ducted, Low Static Ducted Bottom Return
L1
5k to 9k
0.31
27 Low Static Ducted, Low Static Ducted Bottom Return
L2
12k to 18k
0.42
28 Low Static Ducted, Low Static Ducted Bottom Return
L3
21k to 24k
0.55
29 Vertical / Horizontal Air Handling Unit
NJ
12k to 30k
1.04
30 Vertical / Horizontal Air Handling Unit
NJ
36k
1.57
31 Vertical / Horizontal Air Handling Unit
NK
42k to 54k
2.00
32 Floor Standing
CE (U)
7k to 15k
0.37
33 Floor Standing
CF (U)
18k to 24k
0.82
34 HRU: PRHR022A/023A, 032A/ 033A, 042A/ 043A, 063A, 083A
—
—
1.1
35
ADDITIONAL Refrigerant Charge Required (Sum of lines 1 – 34)
36
Total ODU FACTORY Refrigerant Charge
(Choose One)
36A
ARUN024GSS4
0
36B
ARUN038GSS4
0
36C
ARUN048GSS4
0
36D
ARUN053GSS4
0
36F
ARUN060GSS4
0
36G
ARUB060GSS4
0
37
TOTAL SYSTEM CHARGE
Sum of Additional Refrigerant Charge Required (line 35) and Total ODU Factory Refrigerant Charge (from lines 36A through 36G)