68 | STANDARD
MUL
TI V W
all-Mounted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
STANDARD WALL-MOUNTED
General Data
Table 33: Standard Wall-Mounted (SJ Frames) Indoor Unit General Data.
Model No.
ARNU053SJA4
ARNU073SJA4
ARNU093SJA4 ARNU123SJA4 ARNU153SJA4
Cooling Mode Performance
Capacity (Btu/h)
5,500
7,500
9,600
12,300
15,400
Power Input
1
(W)
30
30
30
30
30
H / M / L Power Input at
Factory Default (W)
11 / 10 / 9
12 / 11 / 9
13 / 12 / 9
15 / 13 / 11
23 / 18 / 11
Heating Mode Performance
Capacity (Btu/h)
6,100
8,500
10,900
13,600
17,100
Power Input
1
(W)
30
30
30
30
30
H / M / L Power Input at
Factory Default (W)
11 / 10 / 9
12 / 11 / 9
13 / 12 / 9
15 / 13 / 11
23 / 18 / 11
Entering Mixed Air
Cooling Max (°F WB)
2
76
76
76
76
76
Heating Min (°F DB)
2
59
59
59
59
59
Unit Data
Refrigerant Type
3
R410A
R410A
R410A
R410A
R410A
Refrigerant Control
EEV
EEV
EEV
EEV
EEV
Sound Pressure
4
dB(A) (H/M/L)
30 / 29 / 28
32 / 30 / 28
34 / 32 / 28
37 / 34 / 30
42 / 39 / 32
Net Unit Weight (lbs.)
18.5
18.5
18.5
18.5
18.5
Shipping Weight (lbs.)
24.9
24.9
24.9
24.9
24.9
Communication Cable
5
(No. x AWG)
2 x 18
2 x 18
2 x 18
2 x 18
2 x 18
Fan
Type
Cross Flow
Cross Flow
Cross Flow
Cross Flow
Cross Flow
Quantity
1
1
1
1
1
Motor/Drive
Brushless Digitally Controlled / Direct
Airflow Rate H/M/L (CFM)
240 / 230 / 208
254 / 240 / 208
275 / 254 / 208
300 / 254 / 240
371 / 336 / 240
Piping
Liquid Line (in., O.D.)
1/4 Flare
1/4 Flare
1/4 Flare
1/4 Flare
1/4 Flare
Vapor Line (in., O.D.)
1/2 Flare
1/2 Flare
1/2 Flare
1/2 Flare
1/2 Flare
Condensate Line (in., I.D.)
5/8
5/8
5/8
5/8
5/8
EEV: Electronic Expansion Valve
Power wiring is field supplied and must comply with the applicable local and national
codes.
This unit comes with a dry nitrogen charge.
All capacities are net with a combination ratio between 95-105%.
Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change
without notice. Current certified ratings are available at
www.ahridirectory.org
.
1
Max. power input is rated at maximum setting value.
2
Low ambient performance with LGRED° heat technology is included in Multi V 5 Air
Source Units produced after February 2019.
3
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or
destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F)
under section 608 of CAA.
4
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5
All communication cable to be minimum 18 AWG, 2-conductor, twisted, stranded, shielded
and must comply with applicable local and national codes. Ensure the communication
cable is properly grounded at the master outdoor unit only. Do not ground the ODU-IDU
communication cable at any other point.