ART COOL GALLERY
Electrical Data
Model Number
Voltage
Range
MCA
MOP
Rated
Amps (A)
Power Supply
Power Input (W)
Hz
Volts
Phase
Max.
Cooling
Max.
Heating
H / M/ L at
Factory Default
SF Frames
ARNU093SFA4
187-253
0.4
15
0.3
60
208-230
1
35
35
28 /16 / 10
ARNU123SFA4
0.4
15
0.3
35
35
32 / 20 /12
Table 2: Art Cool Gallery Wall-Mounted Indoor Unit Electrical Data.
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of fuse, use the circuit breaker.
M