22 | ART COOL
TM
MUL
TI V W
all-Mounted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Heating Capacity Tables
ARNU093SFA4
ART COOL
TM
GALLERY
Model No./
Capacity Index
Outdoor
Air Temp.
Indoor Air Temperature (°F DB)
59
61
64
67
70
73
76
80
°F DB °F WB
TC TC
TC
TC
TC
TC
TC
TC
MBh MBh MBh MBh MBh MBh MBh MBh
ARNU093SFA4/
9.6
-21.6
-22.0
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
-17.1
-17.5
6.2
6.2
6.2
6.2
6.1
6.1
6.1
6.1
-12.6
-13
6.9
6.9
6.9
6.9
6.8
6.8
6.8
6.8
-7
-7.6
7.1
7.1
7.1
7.1
7.0
7.0
7.0
7.0
-4
-4.4
7.3
7.3
7.3
7.3
7.2
7.2
7.2
7.2
0
-0.4
7.5
7.5
7.5
7.5
7.5
7.4
7.4
7.4
5
4.5
8.5
8.4
8.3
8.3
8.3
8.3
8.3
8.3
10
9
8.8
8.8
8.8
8.7
8.7
8.7
8.7
8.7
15
14
9.4
9.4
9.4
9.4
9.4
9.4
9.3
9.2
20
19
9.9
9.9
9.9
9.9
9.7
9.7
9.5
9.4
25
23
10.4 10.4 10.4 10.4 10.4 10.1 10.0
9.5
30
28
10.6 10.6 10.6 10.6 10.6 10.4 10.0
9.5
35
32
10.9 10.9 10.9 10.9 10.8 10.6 10.0
9.5
40
36
11.3 11.3 11.3
11.3 10.9 10.6 10.0
9.5
45
41
11.8 11.8 11.8
11.5 10.9 10.6 10.0
9.5
47
43
12.2 12.1 12.0
11.5 10.9 10.6 10.0
9.5
50
46
13.1 12.5 12.0
11.5 10.9 10.6 10.0
9.5
55
51
13.4 12.6 12.0
11.5 10.9 10.6 10.0
9.5
60
56
13.4 12.6 12.0
11.5 10.9 10.6 10.0
9.5
Table 10: ARNU093SFA4 Heating Capacity Table.
Low ambient performance with LGRED° heat technology is included in Multi V 5 Air Source Units produced after February 2019.
TC: Total Capacity (MBh).
The System Combination Ratio must be between 50–130%.
Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change
without notice.
Current certified ratings are available at
www.ahridirectory.org
.
For outdoor unit performance data, see the respective outdoor unit performance data
manuals on
https://lghvac.com/commercial
.