70 | STANDARD
MUL
TI V W
all-Mounted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
STANDARD WALL-MOUNTED
Electrical Data
Model Number
Voltage
Range
MCA
MOP
Rated
Amps (A)
Power Supply
Power Input (W)
Hz
Volts
Phase
Max.
Cooling
Max.
Heating
H / M/ L at
Factory Default
SJ Frames
ARNU053SJA4
187-253
0.31
15
0.25
60
208-230
1
30
30
11 / 10 / 9
ARNU073SJA4
0.31
0.25
30
30
12 / 11 / 9
ARNU093SJA4
0.31
0.25
30
30
13 / 12 / 9
ARNU123SJA4
0.31
0.25
30
30
15 / 13 / 11
ARNU153SJA4
0.31
0.25
30
30
23 / 18 / 11
SK Frames
ARNU183SKA4
187-253
0.65
15
0.52
60
208-230
1
53
53
32 / 26 / 16
ARNU243SKA4
0.65
0.52
53
53
39 / 26 / 16
SV Frames
ARNU303SVA4
187-253
0.64
15
0.51
60
208-230
1
67.0
67.0
54 / 43 / 31
ARNU363SVA4
1.02
0.81
104.0
104.0
85 / 51 / 36
Table 35: Standard Wall-Mounted Indoor Unit Electrical Data.
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of fuse, use the circuit breaker.
M
ax. power input is rated at maximum setting value.