PIPING AND WIRING FOR OUTDOOR UNIT
ENGLISH
Electric Heater Wiring
CAUTION
!
Power Cable Specification : The power cord connected to the electric heater should be
complied with IEC 60245 or HD 22.4 S4(Rubber insulated cord, type 60245 IEC 66 or
H07RN-F)
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or
similarly qualified persons in order to avoid a hazard.
20 mm
GN/YL
1 Phase(Ø)
NORMAL
CROSS-SECTIONAL
AREA 4 mm
2
(For 2kW, 4kW)
(For 6kW)
(For 4kW)
Additional bridge Wire
from L3 to L2
NORMAL
CROSS-SECTIONAL
AREA 4 mm
2
3 Phase(Ø)
20 mm
GN/YL
N
L
G
L1
L2
L3
N
G
N
L
G
L1
L2
L3
N
G
T
S
L
N
G
L1
L2
L3
N
G
External power
supply
1Ø Electric Heater (2kW)
3Ø Electric Heater (6kW)
1Ø Electric Heater (4kW)
Terminal Block 3
at Indoor unit
External power
supply
Terminal Block 3
at Indoor unit
External power
supply
Terminal Block 3
at Indoor unit
It is necessary to connect
the bridge from L3 to L2