INSTALLATION OF INDOOR UNIT
ENGLISH
A
room
(m
2
)
Minimum opening area AV
min
(cm
2
) (Based on h
0
1.2m)
Total Ref. Amount m
c
(kg)
2.7
2.6
2.5
2.4
2.3
2.2
2.1
2.0
1.9
1
693
664
636
607
578
550
521
493
464
2
614
585
557
528
499
471
442
414
385
3
535
506
478
449
420
392
363
334
306
4
456
427
398
370
341
313
284
255
227
5
377
348
319
291
262
234
205
176
148
6
298
269
240
212
183
155
126
97
69
7
261
232
202
173
143
114
84
54
25
8
232
201
171
140
110
79
49
18
9
202
170
139
107
76
45
13
10
171
139
107
74
42
10
11
140
107
74
41
8
12
109
76
42
8
13
78
44
9
14
47
12
15
16
NOTE
• The value of "Release height (h
0
)“ in this unit is considered 1200 mm to comply to IEC
60335-2-40:2013 A1 2016 Clause GG2.
• For intermediate A
room
values, the value that corresponds to the lower A
room
value from the
table is considered. (If A
room
=10.5 m
2
, consider the value that corresponds to A
room
=10 m
2
.)
• For intermediate m
c
values, the value that corresponds to the higher m
c
value from the
table is considered. (If m
c
= 2.15 kg, the value that corresponds to mc = 2.2 kg is
considered.)
Table 3 - Minimum venting opening area for natural ventilation