113
INSTALLER SETTING
ENGLISH
Mixing circuit
Function to set whether or not to use a installed mixing circuit function using mixing kit.
You can set valve closing time[s] and hysteresis temperature[°C] on screen by yourself.
Activating this function, It allows 2 zones(Circuit1, Circuit2) temperature to be controlled,
separately.
- In case of heating, the temperature of Circuit2 can not be set higher than Circuit1 temperature.
- In case of cooling, the temperature of Circuit2 can not be set lower than Circuit1 temperature.
Setting range
- Mixing circuit setting : Use / Not Use
- Value Closing Time : 60 ~ 999 s (Default: 240)
- Hysteresis (Thermal On / Off ) : 1 ~ 5 °C (Default: 2)