Water cooling set temp
Determine cooling setting temperature range when water temperature is selected as setting
temperature.
• In the installer setting list, select water cooling set temp category, and press [OK] button to
move to the detail screen.
* Upper / lower limit / default value is in °C
NOTE
Water condensation on the floor
• While cooling operation, it is very important to keep leaving water temperature higher than
16 °C. Otherwise, dew condensation can be occurred on the floor.
• If floor is in humid environment, do not set leaving water temperature below 18 °C.
NOTE
Water condensation on the radiator
• While cooling operation, cold water may not flow to the radiator. If cold water enters to the
radiator, dew generation on the surface of the radiator can be occurred.
Value
Default
Range
Cooling temp. setting
Max.
24
27~22
All
Min.
18
5~20
Outlet
FCU use
16~20
FCU not used
10~20
Inlet
FCU use
20
20
FCU not used